Viessmann Boiler: Replace ignition electrode block
Replace ignition electrode block on a Viessmann boiler: Replaces the ignition electrode block and gasket on the burner door.
Applies to: Ignition electrodes
How to fix replace ignition electrode block: step by step
- Disconnect the ignition cables from the ignition electrodes.
- Remove the two M6 (5 mm hex) screws and washers, then the electrode block from the burner door.
- Remove the gasket.
- Remove the four M12 burner door bolts. Disconnect the gas line and plugs as in the ionization block procedure.
- Fit the new block and gasket.
- Open the burner door and check the electrode-to-electrode and electrode-to-burner dimensions. Adjust if needed.
- Tighten the M12 bolts and M6 screws to the torque in the torque table.
- Reassemble in reverse order.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.