Viessmann Boiler: Replace gas valve (natural gas)
Replace gas valve (natural gas) on a Viessmann boiler: Remove and replace the NG gas valve on the manifold, then leak test.
Applies to: Gas valve for natural gas
How to fix replace gas valve (natural gas): step by step
- Disconnect the black plug from the gas valve and remove its screw.
- Disconnect the white plug marked GDW2 from the gas pressure switch and remove its screw.
- Disconnect the white plug from the gas pressure switch and remove its screw.
- Remove the four M5 (4 mm hex) screws from the lower gas valve flange and set them aside.
- Disconnect the gas supply line.
- Disconnect the compensation tubing from the gas valve.
- Remove the tube support and set it aside.
- Remove the four M5 (8 mm hex) nuts from the gas manifold and set them aside.
- Clean the manifold surface and replace the O-ring.
- Fit the new gas valve, installing M5 studs and torquing them as specified.
- Reinstall in reverse order and torque the fasteners.
- Leak test all reconnected gas line and valve connections.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.