Viessmann Boiler: Replace gas valve (LPG)
Replace gas valve (LPG) on a Viessmann boiler: Gas valve swap on a boiler set up for propane, including the LPG orifice and gaskets.
Applies to: Liquid propane (LPG)
How to fix replace gas valve (lpg): step by step
- Unplug the black valve connector and the white GDW2 and white gas pressure switch connectors.
- Remove the four M5 (4 mm hex) flange screws and set them aside.
- Disconnect the gas supply line and the compensation tubing.
- Remove the tube support and the four M5 (8 mm hex) manifold nuts.
- Remove the LPG orifice and both LPG gaskets. Replace the gaskets and clean the manifold surface.
- Install M5 studs in the new valve and tighten to the torque in the torque table.
- Reassemble in reverse order.
- Leak test the gas line and valve connections.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.