Viessmann Boiler: Replace burner fan
Replace burner fan on a Viessmann boiler: Burner fan and venturi assembly. Not for the CM2 186.
Applies to: CM2 246, 311 and other models except CM2 186
How to fix replace burner fan: step by step
- Loosen the retaining clamp and disconnect the combustion air flex hose.
- Disconnect the gas line.
- Unplug fan plugs 100 and 100A. Disconnect the APS1 pressure switch tube from the venturi.
- Unplug plugs 35, 36, 87, 111 and 122 from the burner control. Remove the burner control cover to reach plugs 87 and 111.
- Remove the four M8 (13 mm hex) nuts that connect the fan to the burner door.
- Remove the six M8 (13 mm hex) bolts and washers that connect the fan to the venturi.
- Replace the two fan/burner door gaskets in their original order and orientation.
- Move the test port nipple from the old fan to the new fan. Tighten to 27 lb/in (3 Nm).
- Tighten the fan-to-venturi bolts to 53 lb/in (6 Nm) and the fan-to-burner door nuts to 53 lb/in (6 Nm). Keep the original orientation.
- Leak test the reconnected gas line.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.