Viessmann Boiler: Replace an air pressure switch
Replace an air pressure switch on a Viessmann boiler: Remove the display unit and the hoses first. Observe torque values when reassembling.
Applies to: LDW1 and LDW2 air pressure switches
How to fix replace an air pressure switch: step by step
- Undo the 2 mounting screws (1 Nm / 9 lb.in) and remove the display and programming unit from the burner control unit.
- Pull connector aCA (LDW1) and connector aCAA (LDW2) from the plug-in strip.
- Pull the compensation hose from the connector.
- Undo the screw(s) on the air pressure switch and remove the cover (1 Nm / 9 lb.in).
- Undo the base mounting screws and remove the base.
- Install the new switch in reverse order and set it to the same value as the old one.
- Attach the connection hose to the matching connector.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 63. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.