Other: Boiler tips (part 29 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Read the fault history (Vitotronic 300-K)

Viessmann · Vitotronic 300-K

The 10 most recent faults, including resolved ones, are saved and listed by date.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Fault history.
  3. Select Display?.
  4. Press the exit button to leave.

Read the fault memory (message history)

Viessmann · Vitocrossal 200 CI2 boilers

The 10 most recent faults, including those already fixed, and maintenance messages are saved. They are sorted by date.

  1. Open the service menu and enter password "viservice".
  2. Select "Message history", then "Faults".
  3. To clear the list, use the delete button and confirm.

Read the gateway service LED

Viessmann · Versatronik 585 VI/BACIP

The service LED shows the amount of data exchanged between the gateway and the boilers. It does not show BMS communication.

  1. In a single boiler system, the LED blinks slowly while boiler information is retrieved and speeds up when cascade information is retrieved.
  2. In a multi-boiler system, the LED blinks at a more even rate.

Read the software number

Viessmann · Versatronik 200 controller

The software number with its index identifies the controller version and should be quoted when asking for support.

  1. Open the Software number display in the service area.
  2. Note the number with index (XXX.XX).

Reading and acknowledging fault messages

Viessmann · Vitocrossal 300 CU3A with Vitotronic 200 KW6B

When a fault occurs, the fault symbol and red fault indicator flash and Fault appears. Note the cause and fault code before calling the heating contractor. Repeated acknowledgement in quick succession is dangerous; a repeating fault must be reported.

  1. Press OK to see the cause of the fault.
  2. Press the info button to see system performance and measures you can take first.
  3. Write down the cause and the fault code, for example Outside temp sens 18 and Fault A2.
  4. Acknowledge the fault by following the menu prompts. The message then moves to the menu.
  5. Do not acknowledge fault messages several times in quick succession.
  6. If a fault repeats, notify the heating contractor so the cause can be analysed.
  7. To view an acknowledged fault later, open the extended menu and choose Fault.

Reading and acknowledging service messages

Viessmann · Vitocrossal 300 CU3A with Vitotronic 200 KW6B

When a service is due, the service symbol flashes and Service appears. If the service cannot be done yet, the message comes back the following Monday.

  1. Press OK to see the reason for the service.
  2. Press the info button to see details of the service that is due.
  3. To acknowledge, follow the menu prompts and contact the local heating contractor. The message then moves to the menu.
  4. To view an acknowledged service message later, open the extended menu and choose Service.

Reading and clearing service messages

Viessmann · Vitotronic 300-K MW2C

The display shows a service message when the interval set by the heating contractor is reached. Service messages are shown in yellow.

  1. Tap Confirm on the service message. The footer then shows the service symbol.
  2. To view it later, tap the symbol in the footer to open the list.
  3. If several faults are active, tap Service messages to show them.
  4. Notify the heating contractor. If not done, the message returns the following Monday until the contractor resets the interval.

Reading the boiler nomenclature chart (fuel, efficiency, type)

Viessmann · Vitodens 200 / 222-F nomenclature

The nomenclature chart maps letter codes to fuel type (gas or oil), efficiency class (low temperature, condensing, CHP), boiler type (wall-mounted or floor standing), and the DHW and heating options. The chart columns are not clear enough in the extracted text to read each letter with confidence, so use the printed chart on page 6 of the manual for the exact letter-to-option mapping.

  1. Open page 6 of the Vitodens 222-F B2TB Application Guide and locate the code chart.
  2. Match the fuel type letter (gas or oil) to the boiler's fuel.
  3. Match the efficiency letter (low temperature, condensing or CHP) to the boiler's efficiency class.
  4. Match the wall-mounted or floor-standing letter and the DHW and heating option letters to the model being installed.

Reading the cascade overview symbols

Viessmann · Cascade control home screen

The home screen shows each boiler with a flame and a circle. The flame length shows approximate heating output. The circle colour and marks show whether the boiler is running, available or disabled. The number under the circle is the current output in MBH or kW, depending on the selected units.

  1. Flame length: short for 1 to 33%, medium for 34 to 66%, full for 66 to 100%.
  2. Solid white circle: boiler is enabled by the cascade control and is operating.
  3. Solid grey circle: boiler is available but has not been called for.
  4. Crossed-out circle: boiler is disabled for heat generation.

Reading the fault history

Viessmann · Vitodens 200-W B2HA 19, 28, 35

The 10 most recent faults, including resolved ones, are saved sorted by date. Some faults also show plain text.

  1. Press OK and the second button at the same time for about 4 seconds.
  2. Select Fault history.
  3. Select Display? and press OK to read the code.
  4. Look up the code in the fault code table (pages 71 to 72).

Reading the normal-mode display

Viessmann · Versatronik COMO OT display in normal mode

The display shows the time, set room temperature in °C, weekday (1 = Monday, 7 = Sunday), bus symbol, active heating program, burner and heating status, mode indicator, and current room temperature. If the bus symbol is missing, check the data cable to the boiler. Room temperature can drift about ±1°C (±2°F) from the set point, and it can deviate more during the change from reduced to heating operation.

  1. If the bus symbol does not show, check the data cable to the boiler.
  2. Do not treat a ±1°C (±2°F) difference from set point as a fault.

Reading the Vitocrossal model nomenclature

Viessmann · Vitocrossal 300 CU3A

Segment code CU is the Vitocrossal boiler line. The first digit gives the series, so 3 means the 300 series. The domestic hot water code after the series digit shows the DHW capability: X means no DHW, I means indirect DHW, C means on-demand DHW, and T means stratified loading tank. The remaining letters and digits describe the efficiency and fuel type and are not fully legible on these pages, so check the technical data for the exact unit.

  1. Find the segment code (CU) to confirm the Vitocrossal line.
  2. Read the series digit: 3 = 300 series.
  3. Check the DHW code: X no DHW, I indirect DHW, C on-demand DHW, T stratified loading tank.
  4. Confirm the rest of the model code against the Technical Data Manual before ordering or specifying.

Reading the Vitodens boiler nomenclature

Viessmann · Vitodens 200 / 222-F nomenclature

The model code is built from segments. The boiler segment is shown first (VD = Vitodens). The next digit gives the series (1 = 100 series, 2 = 200 series). The domestic hot water capability follows (X = no DHW, I = indirect DHW, C = on-demand DHW, T = stratified loading tank). The page also shows the heating circuit and zone counts, the number of boilers and supply temperatures, and how the system is zoned (ZP = pumps, ZV = zone valves, TV = thermostatic radiator valves, C = combination).

  1. Read the boiler segment (VD = Vitodens) and the series digit (2 = 200 series).
  2. Read the domestic hot water letter (X, I, C or T) to confirm the DHW type.
  3. Read the circuit codes (HC = heating circuit, ZC = zone circuit, HC/ZC = combination) and the number of circuits.
  4. Read the zoning code (ZP, ZV, TV or C) to confirm how the system is zoned.
  5. Check the drawing version and the number of boilers and supply temperatures in the code against the job drawings.

Recommended minimum service clearances

Viessmann · B2TB 68 and B2TB 125

Top, sides, vent pipe, front (alcove or closet) and rear clearances are all printed as 0. Floor is listed as combustible. The boiler passed the zero-clearance-to-combustibles test under ANSI Z21.13 / CSA 4.9 and is listed for zero clearance when vented with the single-wall special venting system (AL-29-4C). This zero clearance supersedes the clearance printed on the venting system label.

Recommended test equipment

Viessmann · All Vitodens 200-W B2HB models

Calibrated test equipment is required: multimeter, flue gas analyzer for CO2 or O2, gas pressure manometer, stack thermometer, efficiency calculator, and CO meter. Cleaning supplies and approved leak detection fluid and pipe sealant are also needed.

  1. Use a multimeter for 0 to 230 VAC, 0 to 12 A and 0 to 100 mA DC.
  2. Use a flue gas analyzer that measures % CO2 or O2.
  3. Use a manometer for gas pressure from 0 to 11 in. w.c. and up to 28 in. w.c., or a Magnehelic.
  4. Use a stack thermometer from 0 to 500 °F (0 to 260 °C).
  5. Use a CO meter from 0 to 400 ppm.
  6. Use approved leak detection fluid for natural gas and liquid propane gas.

Record altered high limit settings

Viessmann · KW10B

Note any changed high limit settings in the technical data table so the next technician can see them.

  1. Compare the current high limit settings with the factory defaults.
  2. Write any altered values in the altered settings column of the technical data table.

Record the serial number when ordering parts

Viessmann · WB1B-26, WB1B-35

The boiler has a 16-digit bar code serial label and a 12-digit ASME/NB serial on a plate riveted to the heat exchanger. The two serials match, so either one is enough when ordering replacement parts.

  1. Locate the 16-digit bar code label on the boiler or the 12-digit ASME/NB plate on the heat exchanger.
  2. Give either serial number when ordering parts.

Record water quality values

Viessmann · Vitocrossal 200 CI2 boilers

Enter the amount of top-up water, total hardness and pH in the appendix table on page 94. The pH must be between 8.2 and 9.5. Water quality requirements are on page 95.

  1. Measure the top-up water amount, total hardness and pH.
  2. Enter the values in the table on page 94.
  3. Confirm pH is between 8.2 and 9.5.

Reduced mode and boost examples

Viessmann · Vitotronic 200-H mixing valve circuit, coding addresses F8, F9, FA, Fb

Example 1 (F8 −5, F9 −14): below −5 °C outdoor the reduced room set point rises with falling outdoor temperature, and below −14 °C it equals the standard room set point. Example 2 (FA 20, Fb 30): when switching from reduced to standard room temperature, the supply set point is raised by 20 % for 60 minutes.

Reduced mode on underfloor heating

Viessmann · Underfloor heating systems

Underfloor heating responds very slowly to short temperature changes. Night setback or Economy mode during short absences saves little energy on this type of system.

Refitting the top and front panels

Viessmann · Vitocrossal 300 CU3A boiler jacket

Panels are refitted in reverse order of removal, using the parts removed earlier.

  1. Place the control cover on the control connection housing and slide it into place.
  2. Install the nuts removed earlier onto the threaded studs.
  3. Place the top jacket panel on the boiler and slide it into place.
  4. Fasten the top panel with the retaining screws removed earlier.
  5. Place the front cover onto the locating pegs.
  6. Push the top of the front panel into place.
  7. Secure the front panel with the retaining screw.

Reinstalling the front enclosure panel

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Refit the front panel. Locking screws must be fitted before the boiler is operated. Never run the boiler without the front cover in place.

  1. Set the front enclosure panel on the guide rails and push it into place.
  2. Tighten the screws at the bottom.
  3. Insert the external accessories connection box cover in place.

Remote burner disable: freeze-up protection warning

Viessmann · Switching Module-V

While the external burner disable contact is closed, freeze-up protection of the heating system and boiler protection cannot be guaranteed.

Remote control only settings

Viessmann · Vitotronic 200-H HK1S/HK3S

Some settings can only be made on the remote control, not on the control unit. Example: normal room temperature on the ts selector knob.

Remove and reinstall burner assembly

Viessmann · Vitodens 200-W B2HA

Burner removal and refit, including gasket replacement and a gas leak test after reassembly. Do not lay the burner on its cylindrical tube or touch the tube mesh, as this can damage it.

  1. Switch off the main power and the ON/OFF switch on the boiler control.
  2. Shut off the gas valve.
  3. Fold down the control unit and remove the cover.
  4. Disconnect the cables from the fan motor, gas valve, ionization electrode and ignition module.
  5. Release the gas supply pipe fitting. Note the gasket between gas valve and fitting.
  6. Loosen the six Torx T-30 screws and remove the burner.
  7. Check the burner gasket for damage. Generally replace it every 2 years.
  8. Refit the burner and tighten the screws in a diagonal pattern to 70 lb.in (8 Nm).
  9. Fit a new gasket on the gas line connection and tighten to 132 lb.in (15 Nm).
  10. Reconnect the electrical cables.
  11. Perform a gas leak test.

Remove the boiler front cover

Viessmann · Vitocrossal 300 CU3A

Needed to reach the serial number label and the siphon.

  1. Remove the retaining screw and set it aside.
  2. Pull the top of the boiler cover away from the boiler.
  3. Lift the cover off and set it aside.

Remove the front cover

Viessmann · Vitodens 100-W service access

The front cover is held by two retaining tabs at the top.

  1. Push up on the two retaining tabs with a screwdriver.
  2. Pull the bottom edge of the cover out.
  3. Lift the cover off.

Removing the front panel

Viessmann · Vitodens 100-W B1HE and B1KE

The front panel is held by a lock on its underside. Protective caps on the heating water and gas connections should stay on until just before installation.

  1. Unlock the front panel from the underside by pushing in with a screwdriver or similar tool.
  2. Swivel the front panel forward slightly.
  3. Lift the panel upward and away.
  4. Leave connection caps on until ready to connect.

Replace an air pressure switch

Viessmann · LDW1 and LDW2 air pressure switches

Remove the display unit and the hoses first. Observe torque values when reassembling.

  1. Undo the 2 mounting screws (1 Nm / 9 lb.in) and remove the display and programming unit from the burner control unit.
  2. Pull connector aCA (LDW1) and connector aCAA (LDW2) from the plug-in strip.
  3. Pull the compensation hose from the connector.
  4. Undo the screw(s) on the air pressure switch and remove the cover (1 Nm / 9 lb.in).
  5. Undo the base mounting screws and remove the base.
  6. Install the new switch in reverse order and set it to the same value as the old one.
  7. Attach the connection hose to the matching connector.

Replace the boiler secondary temperature sensor (15A / 15B)

Viessmann · Boiler secondary temperature sensor 15A / 15B

The secondary sensor sits on each boiler section pressure vessel. Its plug is at the burner control unit for that section.

  1. Remove the spring clip from the sensor well and set it aside.
  2. Pull the boiler secondary temperature sensor out of the sensor well.
  3. Disconnect sensor cable plugs 15A / 15B.
  4. Connect the new sensor to plugs 15A / 15B and install it in the sensor well.
  5. Reinstall the spring clip.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.