Viessmann Boiler: Replace air pressure switch
Replace air pressure switch on a Viessmann boiler: Replace the air pressure switch on the burner control bracket.
Applies to: APS1 (blower) and APS2 (combustion chamber)
How to fix replace air pressure switch: step by step
- Disconnect the air tube from the air pressure switch.
- Remove the M6 (5 mm hex key) screw and the ground wire from the control bracket. Loosen the second bracket screw and pivot the bracket aside.
- Remove the two cover screws and the cover.
- Remove the two M4 (3 mm hex key) screws and the pressure switch.
- Loosen the two programming unit screws to reach the switch cable connector.
- Cut the cable tie, release the connector locking tab and remove the cable.
- Reinstall the new switch. Tighten the bracket M6 screw to the torque in the torque table.
- Make sure the ground wire is secure. Set the new air pressure settings to match the old switch exactly.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.