Viessmann Boiler: Remove the burner (CI2 399 to 2000)
Remove the burner (CI2 399 to 2000) on a Viessmann boiler: Burner removal for service. Burner weights: 399/500 MBH 25 lb (11.3 kg); 750/1000 MBH 35.5 lb (16.1 kg).
Applies to: Vitocrossal 200 CI2 399 to 2000 MBH
How to fix remove the burner (ci2 399 to 2000): step by step
- Prepare the system for servicing per the burner/combustion chamber preparation chapter (page 20).
- Disconnect the burner gas line.
- Disconnect the cable to the burner control unit (BCU).
- If present, remove the combustion air intake hose; on CI2 1500 to 2000 remove the burner venturi and set it aside.
- Remove the 4 burner mounting bolts per burner and remove the burner.
- Rotate the burner and hook it into the burner maintenance bracket.
- Do not damage the burner gauze assembly mesh.
- Check the burner gasket on removal and replace if damaged.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 27-28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.