Viessmann Boiler: Relay test of outputs and pumps
Relay test of outputs and pumps on a Viessmann boiler: Forces individual relay outputs and mixing valve motors on or off to confirm wiring and operation. Selectable outputs include output 20, output 52 (open, hold, closed), DHW pump, DHW re-circulation pump, heating circuit pumps M2 and M3, mixing valve M2 and M3 open/closed, and fault messaging. The illuminated heating circuit selector shows which circuit is active. To reverse the mixing valve motor rotation, refer to page 41.
Applies to: Vitotronic 200-H
How to fix relay test of outputs and pumps: step by step
- Press 9 and OK together for about 2 seconds to start the relay test.
- Use the arrow keys to switch the relay output on or off.
- Press OK to finish the relay test.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
More service & test modes tips for boiler
Source: Vitotronic 200-H installation and service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.