Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Reinstalling the burner after service

Updated · by Aurora Star Tech Inc.

Reinstalling the burner after service on a Viessmann boiler: Burner refit sequence with torque values and gas connection checks.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 100-W WB1B

How to fix reinstalling the burner after service: step by step

  1. Replace the electrical cables from the fan motor, mount the burner, and diagonally tighten the 4 Torx T-30 screws to 4 Nm (35 lb.in.).
  2. Insert a new gasket and tighten the gas connection pipe fitting to 15 Nm (132 lb.in.).
  3. Plug the Venturi extension into the fan.
  4. Replace the electrical cables from the gas valve and the electrode block.
  5. Open the gas shutoff valve and switch on the power supply.
  6. Check the gas connection for tightness.
  7. Install the front panel (see page 52).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

WB1AWB1B

Source: Vitodens 100-W WB1B installation and service instructions, p. 72. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair