Viessmann Boiler: Recommended minimum service clearances
Recommended minimum service clearances on a Viessmann boiler: Top, sides, vent pipe, front (alcove or closet) and rear clearances are all printed as 0. Floor is listed as combustible. The boiler passed the zero-clearance-to-combustibles test under ANSI Z21.13 / CSA 4.9 and is listed for zero clearance when vented with the single-wall special venting system (AL-29-4C). This zero clearance supersedes the clearance printed on the venting system label.
Applies to: B2TB 68 and B2TB 125
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Vitodens 222-F B2TB application guide, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.