Viessmann Boiler: Read ionization current on the control unit
Read ionization current on the control unit on a Viessmann boiler: Shows the flame ionization current through the burner control unit. A multimeter or Testomatic Gas cannot measure it.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner control unit GW6C
How to fix read ionization current on the control unit: step by step
- Press the service button for about 2 sec until the indicator blinks.
- Set Service to 5, press the button, then set Status to 3 and confirm.
- The ionization current in operation appears under Service (for example 30 = 3.0 µA).
- Start the burner with the emissions test switch on the GW6C control and read the value.
- Record the reading in the maintenance record on page 158.
- Exit the menu: press the service button for about 2 sec, set Service to 5, confirm, set Service to 0 and confirm.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.