Pressure relief valve installation and discharge piping on a Viessmann boiler: The pressure relief valve mounts on the top of the boiler or on the boiler safety supply. Nothing that can shut off or block flow may be between the boiler and the relief valve or on its discharge side. The discharge pipe keeps the same size as the outlet, runs horizontally over the side of the boiler and then down to about 1 ft (300 mm) above the floor, as close to a floor drain as possible. Do not pipe the discharge outdoors or to any place where it can freeze.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CI2 399 to 2000

How to fix pressure relief valve installation and discharge piping: step by step

  1. Mount the relief valve on the top of the boiler or the boiler safety supply.
  2. Do not install any valve or obstruction between the boiler and the relief valve.
  3. Keep the discharge pipe the same size as the relief valve outlet.
  4. Run the discharge horizontally over the side of the boiler, then vertically down to about 1 ft (300 mm) above the floor.
  5. Route the discharge close to a floor drain and not outdoors or where freezing can occur.
  6. Secure the discharge piping with hangers or brackets.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

More commissioning tips for boiler

Source: Vitocrossal 200 CI2 Installation Instructions, p. 40. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.