Viessmann Boiler: Pre-test checks before high limit safety cut-out test (CSD-1)

Updated · by Aurora Star Tech Inc.

Pre-test checks before high limit safety cut-out test (CSD-1) on a Viessmann boiler: Checks to make before testing the boiler high limit controls. Viessmann says the high limit is set at a fixed 210°F (99°C) and needs a manual reset after it trips.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CI2 gas condensing boilers

How to fix pre-test checks before high limit safety cut-out test (csd-1): step by step

  1. Check the heating system pressure. Operating range is 15 psi (1.0 bar) minimum to 80 psi (5.5 bar) maximum.
  2. For room air dependent operation, confirm the combustion air openings in the mechanical room are open.
  3. For room air independent direct vent operation, confirm the air pipes are unobstructed.
  4. Check the gas supply pressure against the target value in the table on page 24.
  5. Open the gas line shut-off valves.
  6. Check the neutralizing system, if installed, including the hydraulic seal in the condensate trap.
  7. Check all gaskets and plugs and retighten if needed.
  8. Check heating water side connections for leaks after about 500 hours of run time.
  9. Switch on the boiler power at the breaker, then power on the control unit.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 Service Instructions, p. 10. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.