Viessmann Boiler: PP(s) and CPVC vent system limits
PP(s) and CPVC vent system limits on a Viessmann boiler: PP(s) vent is flame-retardant polypropylene rated to a maximum of 230 F (110 C) and must be listed to ULC S636 or UL 1738. Do not mix pipe, fittings, or joining methods from different vent makers. CPVC vent must be Type BH Class IIB 90 C.
Applies to: PP(s) and CPVC venting
How to fix pp(s) and cpvc vent system limits: step by step
- Confirm PP(s) components are listed to ULC S636 or UL 1738.
- Do not mix vent brands, fittings, or joining methods.
- For CPVC, use Type BH Class IIB 90 C pipe.
- For an existing vent reused with this boiler, seal it so room air cannot be drawn in as combustion air and confirm it is clean and in good condition.
- Count the vent and combustion air length in the equivalent length.
- If flexible vent or flexible air intake is used, reduce the maximum equivalent length by 25%.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Installation Instructions, pp. 52-53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.