Viessmann Boiler: Perform LON participant check
Perform LON participant check on a Viessmann boiler: Tests communication between the fault manager and the connected LON devices. Requires the control unit set as fault manager (code 79:1), participant numbers set in all units, and an up-to-date participant list.
Applies to: Vitotronic fault manager on LON system
How to fix perform lon participant check: step by step
- Press OK together with the second service key (symbol not legible on the page) for about 4 seconds.
- Select Service functions.
- Select Participant check.
- Select the participant to test, e.g. participant 10.
- Read the result: OK means passed, Not OK means failed.
- To run a new check, create a new participant list using Delete list in the menu.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
More service & test modes tips for boiler
Source: Vitodens 222-F B2TB service instructions, p. 45. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.