Viessmann Boiler: Open access to combustion controller coding
Open access to combustion controller coding on a Viessmann boiler: Coding address 11 must be set to 11:9 before combustion controller coding addresses and the LPG setting (82:1) can be changed. Otherwise those addresses stay locked.
Applies to: Vitodens 200-W B2HA, coding access
How to fix open access to combustion controller coding: step by step
- Go to General coding 2.
- Set address 11 to 9 to open access to combustion controller coding.
- Change the required combustion or LPG addresses.
- Set address 11 back to a value other than 9 when finished, if locking is wanted.
If the unit shows an error code, look it up: Viessmann Boiler codes
More access & passwords tips for boiler
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 48, 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.