Access & passwords: Boiler tips (part 3 of 4)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on access & passwords for boiler. Check each one against the manual for your exact model before acting.

Factory passwords and changing them

Viessmann · Vitocrossal 300 CA3B Dual Fuel

Factory passwords are viservice for the service main menu and viexpert for Coding Level 2. A password can be changed by the technician. Resetting all passwords needs a master password from Viessmann Technical Service.

  1. From the home screen, tap Service and enter the viservice password.
  2. Tap Change passwords.
  3. Choose Service level or Coding level 2.
  4. Enter the current password and confirm.
  5. Enter the new password and confirm.
  6. To reset all passwords, request the master password from Viessmann Technical Service, then choose Reset all passwords and enter it.

Factory passwords and Coding level 2 access

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

Factory passwords are viservice for the service main menu and viexpert for Coding level 2. Coding level 2 is only shown in the menu after the viexpert password has been entered.

  1. Enter viexpert in the service menu to enable Coding level 2.
  2. Tap the return button to go back to the Service main menu.

Flip-down cover and adjustable values

Viessmann · Vitotrol 300 remote control

Values are changed with the flip-down cover open. Flashing values in the display can be changed. If the heating contractor has locked a setting by coding, the display shows "without function".

  1. Open the flip-down cover of the remote control to make changes.
  2. Check for flashing values; only flashing values can be changed.
  3. If the display shows "without function", the setting is locked by coding and must be changed by the heating contractor.

Gateway web login default

Viessmann · Versatronik 505 BACnet IP gateway configuration pages

Default gateway configuration login is admin / admin. It can be renamed on the Change Password screen.

  1. Change the default password during commissioning and record the new one.

Home screen and locked panel

Viessmann · Vitocrossal 200 CI2 control unit

After the control unit starts, the home screen is shown. Factory setting is the heating circuit or continuous operation display. The home screen can be set to show DHW, dashboard or cascade status instead. If operation of the home screen has been blocked, the display shows Panel locked and no adjustments can be made on the home screen or in the main menu.

  1. If the standby display is active, tap anywhere on the screen to wake it.
  2. To reach the home screen from the main menu, tap the home button.
  3. If Panel locked appears, the operator lock is active. Unlock it via the settings described on p. 25.

Lag boiler section service displays

Viessmann · Vitocrossal 300 CA3B multi and single boiler applications

Service display access depends on which section is in fault or service condition.

  1. For boiler sections B and C, open the lower front boiler panel and control cover.
  2. For boiler section A on a 2nd, 3rd or 4th boiler, open the top front panel and control cover if the fault requires it.
  3. In single boiler applications, no panels need to be opened to set up the controls.

Leave the service menu

Viessmann · Service menu

The service menu exits automatically after 30 minutes without use.

  1. From the service main menu tap Exit service.
  2. Confirm Terminate service? with OK.

Lock the controls (Level 1 or Level 2)

Viessmann · Control panel

Level 1 keeps all functions on the default displays operable and disables the rest. Level 2 disables all functions. The default password is 'viessmann' and can be changed.

  1. Open Settings.
  2. Select 'Lock panel'.
  3. Select 'Lock everything' or 'Only home screen operable'.
  4. Enter the password 'viessmann'.
  5. Confirm.

Log in to gateway configuration pages

Viessmann · Versatronik 585 VI/BACIP

The gateway has a built-in web configuration page. Default login is admin / admin. You can rename the password on the Change Password screen.

  1. Connect your computer directly to the gateway BACnet port with no other devices attached.
  2. Set the computer to automatic IP (DHCP), or set its IP address to 192.168.88.90 with subnet mask 255.255.255.0.
  3. Power-cycle the gateway (power off, then on).
  4. Open a browser and go to http://192.168.88.89/admin.
  5. Log in with the default user name and password admin (no quotes), or with your changed password.

Open access to combustion controller coding

Viessmann · Vitodens 200-W B2HA, coding access

Coding address 11 must be set to 11:9 before combustion controller coding addresses and the LPG setting (82:1) can be changed. Otherwise those addresses stay locked.

  1. Go to General coding 2.
  2. Set address 11 to 9 to open access to combustion controller coding.
  3. Change the required combustion or LPG addresses.
  4. Set address 11 back to a value other than 9 when finished, if locking is wanted.

Open coding level 1

Viessmann · Vitodens 200-W B2HA 112–530

Codes are displayed as plain text.

  1. Press OK and the service key together for about 4 seconds.
  2. Select 'Coding level 1'.
  3. Select the group: General, Boiler, DHW, Solar, Heating circuit 1/2/3, or All codes std device.
  4. Select the coding address.
  5. Select the value and confirm with OK.

Open coding level 2

Viessmann · Vitotronic 200-H HK1B

Coding level 2 gives access to every coding address, including the level 1 codes. Enter it from the normal display with the two-step button sequence below.

  1. Press OK together with the second button shown in the manual and hold for about 4 seconds.
  2. Press OK together with the same button again and hold for about 4 seconds.
  3. Confirm that the display shows 'Coding level 2'.
  4. Choose the group you need: General, DHW, Solar, Heating circuit 1/2/3, or All codes standard unit.
  5. Select the coding address, pick the value from the table and confirm with OK.

Open coding level 2 on the Vitotronic 300-K

Viessmann · Vitotronic 300-K coding

Coding level 2 shows every coding address, including those from level 1. Addresses that do not apply to the installed equipment or to other settings are hidden.

  1. Press OK and the second button shown on the page together for about 4 seconds (button symbol is not legible in this extract).
  2. Repeat the same button press for about 4 seconds again.
  3. Confirm that the display shows 'Coding level 2'.
  4. Select the coding group needed: General, Cascade, DHW, Solar, Heating circuit 1/2/3, or All codes std device.
  5. Select the coding address, choose the value from the tables, and confirm with OK.

Open coding level 2 on Vitotronic 200

Viessmann · Vitotronic 200 (Type HO1B) and Vitotronic 300-K (Type MW2B), coding level 2

Coding level 2 gives access to every coding address, including those in coding level 1. Codes that do not apply to the installed equipment or to other settings are hidden.

  1. Press OK and the second button together for about 4 seconds.
  2. Press OK and the second button together for about 4 seconds again.
  3. Wait for the display to show 'Coding level 2'.
  4. Select the coding group: 'General' or 'Boiler'.
  5. Select the coding address.
  6. Choose the value from the tables and confirm with OK.
  7. To return all codes to factory settings, select 'Standard setting' in coding level 2. This also resets the coding level 1 codes.

Open coding levels 1 and 2

Viessmann · Vitocrossal 300 CA3B, all sizes 2.5 to 6.0

Coding is reached from the home screen through the Service menu. Coding level 1 uses the service password, coding level 2 uses the expert password. Coding is grouped into General, Burner control unit, DHW, Solar, Heating circuit 1/2/3, Boiler, Cascade and All coding. Indicators shown depend on how the system is configured. The Service and System coding buttons appear on the screen; some button icons are missing from the page text.

  1. From the home screen, open the Service menu.
  2. Enter the service password (viservice).
  3. Open System coding or System configuration.
  4. Choose Coding level 1, or Coding level 2 and enter the expert password (viexpert).
  5. Select the coding group.
  6. Set the value from the table for that address and confirm it.

Open information and configuration menu

Viessmann · Vitocrossal 300 CA3B Dual Fuel burner control units

The information and configuration menus open from the operating display. The menu times out after 20 seconds with no button press. Adjust configuration only when the burner control unit is on standby.

  1. Press and hold button S for more than 2 seconds.
  2. Scroll through menu items with the Y and B buttons.
  3. Press button S to select a menu item. It shows under Service.
  4. Press button S or hold it to exit to the operating display.

Open the control panel to reach the menus

Viessmann · Versatronik COMO OT

Operating and changing modes are reached by opening the control panel cover. The display shows USER when the cover is open. Use the Plus and Minus keys to move between levels and values, and the Prog key to select or save.

  1. Open the control panel cover. The display shows USER.
  2. Use Plus/Minus to pick the level (User, Display, Time-Day, HTG Prog 1/2, Holiday, Expert).
  3. Press Prog to open the level.
  4. Use Plus/Minus to find the value, then press Prog to select it. A warning triangle appears when the value can be changed.
  5. Change the value with Plus/Minus.
  6. Press Prog to save, or close the cover without pressing Prog to discard the change.
  7. Close the cover once the value is saved; the warning triangle disappears.

Open the expert level menu

Viessmann · Versatronik 200 expert level

The expert level shows temperatures and status for the circuits and system.

  1. Press the Home button to show the Main Menu.
  2. Turn the rotary dial until Expert Level is shown on the screen.
  3. Press the key beside User to select the menu option.
  4. Select a circuit or menu item to view its temperature and status information.
  5. Press Cancel to leave the current screen.

Open the extended menu

Viessmann · Vitotronic control unit, extended menu

The extended menu holds less frequently used functions such as time programs and holiday programs.

  1. If the screen saver is active, press any key except ?, then press the menu key (symbol not legible in this extract).
  2. If you are somewhere in the menu, press the same menu key.

Open the gateway configuration pages

Viessmann · Versatronik 515 NR2/BACIP and 515D NR2/BACIP gateways

Default login for the gateway web configuration. Change the password on the Change Password screen.

  1. Connect your computer directly to the gateway BACnet interface with no other devices attached.
  2. Set the computer to automatic IP (DHCP), or set its IP address to 192.168.88.90 with subnet mask 255.255.255.0.
  3. Power the gateway off and on again.
  4. Open a browser and go to http://192.168.88.89/admin.
  5. Log in with user name admin and password admin, then change the password on the Change Password screen.

Open the Service menu (password viservice)

Viessmann · Vitodens 200-W B2HE 85, 120, 150, 199

The touchscreen Service menu holds diagnosis, actuator test, parameters, message history and service functions. It closes on its own after 30 minutes.

  1. Menu > Service
  2. Enter the password viservice (factory default)
  3. If passwords were changed and lost, Viessmann Technical Service issues a master password

Open the service menu with password

Viessmann · Vitocrossal 200 CI2 boilers with HMI programming unit

Service functions such as message history, test modes and reset are behind the service menu and need the service password.

  1. Open the main menu on the programming unit (button icon not legible in the text).
  2. Select "Service".
  3. Enter password "viservice".
  4. Confirm with the OK button.

Open the standard menu

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

The standard menu holds the most-used settings for the heating circuit shown in the header. If the screen saver is on, press any key except the one marked ?. If you are already inside a menu, keep pressing until the standard menu appears. If the system has 2 or 3 heating circuits, you can choose which circuit (HC1, HC2 or HC3) shows here.

  1. If the screen saver is on, press any key except ?.
  2. If you are inside another menu, keep pressing until the standard menu appears.
  3. To change which heating circuit is shown, use the operating instructions.

Open the system coding levels

Viessmann · Vitotronic 300 GW6B control unit

Coding is split into groups and two levels. Level 1 uses the viexpert password after viservice.

  1. From the home screen tap Menu.
  2. Tap Service.
  3. Enter the viservice password.
  4. Tap System coding.
  5. Tap Coding level 1 or Coding level 2. For level 1 or 2 enter the viexpert password.
  6. Select the group (General, Combustion controller, DHW, Solar, Heating circuit 1/2/3, Boiler, Cascade or All coding).
  7. Select the coding, tap Edit, then set the value from the coding tables.

Open the user interface programming unit

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The user interface programming unit has two covers, each with a lock. Unlock and slide them open to reach the controls.

  1. Turn both locks to unlock the user interface programming unit covers.
  2. Slide the covers open.

Open the Vitotronic 100 programming unit

Viessmann · Vitotronic 100 GC1B

The programming unit sits behind a flap on the control.

  1. Pull the flap from the top edge forward to open it.

Open the Vitotronic 300-K programming unit

Viessmann · Vitotronic 300-K MW1B

The programming unit sits behind a cover flap on the Vitotronic 300-K.

  1. Pull the flap from its top edge forward to open it.
  2. Use the cursor keys to scroll and set values, OK to confirm or save, the back key to step back or cancel, and the ? key for extra information on the selected option.
  3. Press the extended menu key to open the extended menu.

Opening the control unit cover

Viessmann · Vitotronic 100, GC1

The control unit sits behind a hinged cover. Open it by pulling the top gently toward you. Close the cover again after use.

  1. Pull the top of the hinged cover gently downward toward you to open it.
  2. Close the cover after use.

Opening the programming unit cover

Viessmann · Vitocontrol-S, VD2/CT3/CM2

The control unit sits behind a hinged cover. Open it by pulling the top gently toward you, and close it again after use.

  1. Pull the top of the hinged cover gently downward toward you to open it.
  2. Close the cover again after you finish.

Operating levels and the expert level code

Viessmann · Versatronik 200 System Control menu levels

Settings are sorted into levels: Display (read-only sensor and set point values), User, Time program, Time-Date, Service, Expert level (installer), and Expert level IM (BUS heat source values). Installation, DHW, Heating circuit 1/2 and Solar/MF pages sit under these levels. Expert level values are protected by a code number, and changing them incorrectly can damage the system or cause a malfunction.

  1. Use Display level to read values without risk of changing them.
  2. Enter the expert level code before changing expert settings.
  3. Only change expert values if you know the installation requirements.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.