Viessmann Boiler: Monthly owner/operator checks

Updated · by Aurora Star Tech Inc.

Monthly owner/operator checks on a Viessmann boiler: Routine checks the owner or operator should do each month. Record any deficiency for the heating technician.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CI2, all sizes

How to fix monthly owner/operator checks: step by step

  1. Check the system pressure frequently.
  2. Confirm the boiler control operates correctly per the control instructions.
  3. Inspect all seals and retighten or replace as needed.
  4. Confirm combustion air and ventilation air into and out of the mechanical room is maintained at all times.
  5. Confirm nothing blocks combustion and ventilation air and no chemicals, garbage, gasoline, combustibles or flammable liquids or vapours are stored near the boiler.
  6. Look for water on the floor from the relief valve discharge, any pipe, joint, valve or air vent.
  7. Test the pressure relief valve and confirm it operates properly per the valve instructions.
  8. Check that all operational high limits work properly.
  9. If a condensate neutralization system is fitted, check it works, check the media condition and fill level, and check flue gas condensate pH (minimum 6.5).
  10. Check external vent pipe joints for moisture and check for ice on the vent pipe or chimney outlet in winter.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 service instructions, p. 98. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.