Viessmann Boiler: Modbus register access limits
Modbus register access limits on a Viessmann boiler: The gateway treats holding and input registers as the same data. Holding register 1 is address 40001. Registers 1 to 23 are saved in EEPROM and survive a power cycle. Coil and input status are not used.
Applies to: Versatronik 502 / 502D gateway
How to fix modbus register access limits: step by step
- Read no more than 40 registers in one request.
- Do not go past address 78, or the gateway returns an exception response.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 502 & 502D MODBUS manual, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.