Other: Boiler tips (part 24 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Maximum boiler-to-CombiPLUS distance

Viessmann · Vitodens 100-W WB1B with CombiPLUS

The communication cable limits the distance between boiler and CombiPLUS to 36 in (915 mm), measured with field-supplied fittings and pipes.

Mechanical room conditions

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

Boiler room air quality and conditions affect heat exchanger life and warranty coverage.

  1. Do not install the boiler where chemicals, aggressive vapors (e.g. bleach, hair spray, perchloroethylene), halogenated hydrocarbons, high dust or high humidity are present.
  2. Keep the room frost-protected.
  3. Keep the ambient temperature at or below 95°F (35°C).
  4. Provide good ventilation and do not close or obstruct vents.

Mechanical room disconnect and fuel shut-off

Viessmann · Vitocrossal 200 CI2

Viessmann recommends extra safety shutoffs located outside the boiler room.

  1. Install an extra electrical disconnect switch outside the mechanical room or enclosed installation area.
  2. Install a fuel shut-off valve outside the mechanical room where possible.

Mechanical room location and ambient limits

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Put the boiler in a heated indoor room near a floor drain and close to an outside wall. Room must stay between 32°F and 104°F (0°C and 40°C). Keep halogenated hydrocarbons and heavy dust out of the combustion air and never block existing vents. The wall must carry the full water weight of the boiler.

  1. Confirm the room is heated and stays between 32°F and 104°F (0°C and 40°C).
  2. Check the boiler sits near a floor drain and near an outside wall where the vent can run easily.
  3. Check the wall can carry the full water-filled boiler weight (see Technical Data, p. 99).
  4. Check for chemical or dust sources such as paint solvents, bleaches, refrigerant leaks, or salt before installing.
  5. Leave existing ventilation openings open.

Mechanical room requirements

Viessmann · Boiler room and combustion air

The boiler room must be heated, indoors, and free of contaminated air. Keep fresh combustion air available.

  1. Locate the boiler in a heated indoor space near a floor drain and as close as practical to the chimney or vent.
  2. Place it near an outside wall where fresh air can be ducted directly to the boiler area when possible.
  3. Keep the room at or below 104°F (40°C).
  4. Do not install where chemicals are stored or in rooms with refrigeration equipment.
  5. Do not run exhaust fans unless fresh combustion air provisions are added, such as a fresh air fan.
  6. Install an electrical disconnect and a fuel shut-off valve outside the mechanical room if possible.

Menu level map

Viessmann · Versatronik COMO OT

Top-level menu levels and the manual page for each. Hot water programming (HotWProg) is listed as not available on this page set.

  1. User (p. 18): base control settings.
  2. Display (p. 19): current temperatures and readings.
  3. Time-Day (p. 20): time and weekday.
  4. HTG Prog 1 and HTG Prog 2 (p. 21): timer programs.
  5. Holiday (p. 23): holiday programs.
  6. Expert (p. 24): higher level settings; code-protected values are also here.

Menu structure overview

Viessmann · Vitotronic 300-K MW1B

The Vitotronic 300-K extended menu includes Boiler sequence, Economy mode, Party mode, Standard setting, Test mode, Solar energy and detailed scan options. The standard menu includes Heating, DHW, Settings and Information.

  1. Use the standard menu for everyday heating and DHW settings
  2. Use the extended menu for boiler sequence, test mode, solar and detailed scan options
  3. Use the scan options to read the status of boiler, heating circuits, DHW and solar values

Minimum clearances to combustibles

Viessmann · Vitodens 200-W B2HB 19 to 199

Vitodens 200-W B2HB is listed for zero clearance to combustibles when vented with listed single-wall special venting (AL-29-4C). This listing overrides the clearance printed on the venting label. The clearance row on the page is garbled: most positions read 0, and AL/CL (alcove/closet) is marked in one position. Confirm the exact per-side values from the clean table in the installation instructions before setting the boiler. Service clearance values are titled on this page but not printed in the text.

  1. Confirm the clearance table in the installation instructions before placing the boiler.
  2. Keep the vent pipe to the listed special venting system when using zero clearance.
  3. Leave the service clearances shown in the installation instructions for access.

Minimum water pressure for operation

Viessmann · Vitotron 100 VLN2

The boiler will not run below 7 psi water pressure.

  1. Check the system pressure is at least 7 psi before expecting the boiler to run.

Mixing valve controller accessory kit

Viessmann · Models 45, 57, 160, 199

The mixing valve controller kit works only with wall-mounted gas-fired hot water heating boilers and a weather-responsive control. It can replace a Vitotronic control.

  1. Check that the boiler is wall-mounted, gas-fired, hot water heating, and that a weather-responsive control is used.
  2. Connect the accessory kit to the heating circuit with mixing valve as shown in the manual.
  3. Set coding as described in the Vitodens 200-W B2HB service instructions.
  4. Follow the accessory kit installation instructions for installation.

Mixing valve extension kit sensor and components

Viessmann · Mixing valve extension kit

The mixing valve kit includes a contact-type supply temperature sensor with a 19 ft (5.8 m) cable.

  1. Use the connecting plug for the heating circuit pump.
  2. Use the supply temperature sensor as a contact sensor for the supply temperature.

Mixing valve extension PCB for heating circuits 2 and 3: diagram legend

Viessmann · Vitotronic 300 GW6B extension PCB for heating circuits 2 and 3

Legend for the wiring diagram of the extension PCB that serves heating circuits 2 and 3 with mixing valves. It covers the supply temperature sensors for M2/M3, the heating circuit pumps for M2/M3, the power supply, the mixing valve motors for M2/M3, relays K1 to K6 and the electrical interfaces.

Mixing valve heating circuit

Viessmann · Heating circuits with mixing valve

A mixing valve blends hot boiler water with cooler return water from the heating circuit. The heating circuit pump circulates the blended water. The control adjusts supply temperature through the mixer to suit outdoor conditions. The mixing valve assembly with extension kit is an accessory.

Mixing valve heating circuit and DHW recirculation pump

Viessmann · Heating circuits with mixing valve; DHW recirculation

A mixing valve extension kit (accessory) lets the control run a heating circuit with a mixing valve. The mixer mixes hot boiler water with cooled return water to hold the supply temperature the control calls for. A DHW recirculation pump moves DHW around a loop between the tank and the draw-off points so hot water reaches the tap faster.

Mixing valve motor direction for installation examples

Viessmann · Mixing valve circuits

The factory motor direction is set for the default layout. Change the direction for the installation examples shown on this page. Abbreviations: HR heating return, HV heating supply, KR boiler return, KV boiler supply.

  1. Compare the installation layout with the example diagram.
  2. If the example requires it, reverse the mixing valve motor rotation (see the rotation procedure on page 128).
  3. Refer to the mixing valve installation instructions for insert conversion, if required.

Mixing valve motor wiring for installation examples

Viessmann · Mixing valve motor

As delivered, the mixing valve motor is wired for the installation examples shown. Only change the motor connections when the installation example requires it. Legend: HR heating return, HV heating supply, KR boiler return, KV boiler supply, A marker notch.

  1. Leave the motor wiring as delivered if it matches the installation example.
  2. If a different installation example is used, change the electrical connections of the mixing valve motor as shown for that example.

Modbus register access limits

Viessmann · Versatronik 502 / 502D gateway

The gateway treats holding and input registers as the same data. Holding register 1 is address 40001. Registers 1 to 23 are saved in EEPROM and survive a power cycle. Coil and input status are not used.

  1. Read no more than 40 registers in one request.
  2. Do not go past address 78, or the gateway returns an exception response.

Mounting the 120VAC gateway (502)

Viessmann · Versatronik 502 NR2/MODBUS (120VAC)

The 120VAC unit mounts on a wall near the boiler control. The cover is held by two screws, one on each side of the base.

  1. Mount the gateway near the connected boiler control.
  2. Loosen the two screws on either side of the base and remove the cover.
  3. Fasten the base to the wall with field-supplied screws or fasteners.
  4. Remove a knockout and fit a strain relief or box connector. Remove other knockouts only as needed.
  5. After all 120VAC and low-voltage connections are complete and checked, refit the cover.

Mounting the 24VAC DIN rail gateway (502D)

Viessmann · Versatronik 502D NR2/MODBUS (24VAC)

The 24VAC unit mounts on a DIN rail inside an enclosure near the boiler controls.

  1. Mount the Versatronik 502D on a DIN rail inside an enclosure near the boiler controls.
  2. Make all connections, including the field-supplied 24VAC power connection.
  3. Check the connection overview on the unit: RJ45 control connection, paralleled BUS connection, Modbus A+ and B- connection, and 24VAC power connection.

Mounting the front part of the control unit (CM2 only)

Viessmann · Vitotronic 100 GC1 on CM2 boilers

CM2 boilers only. Refit the front housing of the control unit after wiring.

  1. Fit the front housing hinges into the counterparts on the main housing.
  2. Release the stay bar, open it up and lock it at point A.
  3. Plug the flat cable from the Optolink into socket X20.
  4. Plug the programming unit lead into socket X10 and route it through the cable guides in the cover.
  5. Engage the stay bar in the front housing.
  6. Close the front housing and secure it with the supplied screws.
  7. Fit the control cosmetic cover.

Multi-boiler display numbering

Viessmann · Multi-boiler cascade

In multi-boiler systems each Vitotronic 100 shows its boiler number on the standard display.

  1. Read the boiler number shown on the standard display to know which boiler's temperature is shown.

Multi-boiler system notes

Viessmann · Multi-boiler systems

Some Vitotronic 100, GC1 functions do not work in a multi-boiler system. These include the boiler water temperature change, the domestic hot water temperature change and the heating program selector buttons, which are marked on the controls.

  1. In a multi-boiler system, make boiler water and DHW temperature changes through the Vitocontrol-S, not the individual boiler control.
  2. Note that heating program buttons on the Vitotronic do not function in a multi-boiler system.

Naming heating circuits

Viessmann · Vitocrossal 300 CA3B

Each heating circuit can be given its own name, such as Ground floor. The name then appears in the main menu.

  1. From the home screen, select Settings.
  2. Select Name for heating circuit.
  3. Select Heating circuit 1, 2 or 3.
  4. Enter the name using the keypad.
  5. Confirm.

Natural gas to LPG conversion reference

Viessmann · Vitocrossal 300 CA3B 2.5 to 6.0

Conversion from NG to LPG is covered by the conversion kit instructions.

  1. Refer to the installation instructions supplied with the conversion kit.

Navigation and menu buttons

Viessmann · Vitocrossal 200 CI2 control unit

The navigation area has buttons to return to the home screen, go back one step, end an adjustment in progress, confirm a change, open the help text, open messages, and scroll through the menu. Some icons appear only depending on system version and operating status.

  1. Use the back button to move one step back in the menu.
  2. Use the cancel button to end an adjustment without saving it.
  3. Use the confirm button to save a change.
  4. Use the help button for the help text and the message button to view messages.

nciNR2Config is not user accessible

Viessmann · Versatronik 581 gateway firmware V1.1

The nciNR2Config register cannot be changed by the user. The gateway is preconfigured for 8 Vitotronic 300 GW6B boilers and 3 zones.

Neutralizing unit in condensing system layouts

Viessmann · Vitocrossal 300 and Vitocrossal 200 condensing systems

System types 3, 4 and 5 show a neutralizing unit in the boiler circuit. Include it in the installation as shown in the diagram.

  1. Locate the neutralizing unit in the layout shown for the system type.
  2. Confirm the installation matches the circuit diagram before commissioning.

Never run boiler without venting

Viessmann · Vitodens 200-W B2HA 45, 60

The boiler must never run without an installed venting system. An improper vent can cause carbon monoxide poisoning. All combustion products must be vented outdoors.

Never run the boiler without a complete venting system

Viessmann · Vitorond 200 VD2 boilers

Improper venting can cause carbon monoxide poisoning. All combustion products must be vented safely outdoors. Check the Venting Information section for venting and chimney requirements.

Never run the boiler without a venting system

Viessmann · Vitorond 200 VD2A

The boiler must never operate without an installed venting system. An improper vent can cause carbon monoxide poisoning. All products of combustion must be vented to the outdoors.

  1. Verify the venting system is installed and complete before firing the boiler.
  2. Confirm all combustion products exit to outdoors.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.