Viessmann Boiler: Mixing valve extension kit communication lost (emergency mode)
Mixing valve extension kit communication lost (emergency mode) on a Viessmann boiler: If the PlusBus link to a mixing valve extension kit fails, the affected heating circuit switches to emergency mode after 20 minutes. Until then, the extension outputs hold their last state.
Applies to: Heating circuits with mixing valve extension kit
Common causes of mixing valve extension kit communication lost (emergency mode)
- Communication break on PlusBus to the mixing valve extension kit
How to fix mixing valve extension kit communication lost (emergency mode): step by step
- Check the PlusBus wiring between the HMU and the mixing valve extension kit.
- Check that the extension kit has power.
- Clear the fault once the link is restored and confirm the heating circuit leaves emergency mode.
- Note that the mixing valve is closed and the circuit pump runs while in emergency mode.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.