Applies to: Vitocrossal 200 CI2 gas condensing boilers

How to fix mechanical room prep before installing the boiler: step by step

  1. Use the installation room only for the boiler.
  2. Set the boiler on a load-bearing base at least 4 in. (100 mm) high, and allow for the condensate drain height.
  3. Place the boiler in a heated indoor space, near a floor drain and as close as practical to the vertical chimney or vent.
  4. Where possible, locate it near an outside wall so fresh air can be ducted straight to the boiler area.
  5. Keep the room free of flammable gases and vapors, halogens, solvent vapors and chemical storage.
  6. Check that the combustion air is clean; in pools, watch for chlorine and salts from water treatment.
  7. Do not use exhaust fans unless fresh combustion air is supplied (for example a fresh air fan).
  8. Do not install the boiler in a room with refrigeration equipment.
  9. Keep humidity low, prevent freezing and ensure good ventilation.
  10. Keep the mechanical room at or below 104°F (40°C).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Viessmann Vitocrossal 200 CI2 Installation Instructions, p. 8; p. 3. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977