Viessmann Boiler: Massachusetts side-wall vent CO detector requirements
Massachusetts side-wall vent CO detector requirements on a Viessmann boiler: For side-wall horizontal venting where the vent end is under 7 ft above grade, a hard-wired CO detector with battery backup must be on the floor level of the installation, and CO detectors with alarms on each additional level. A warning sign must be placed 8 ft above grade in line with the vent.
Applies to: Installations in the Commonwealth of Massachusetts
How to fix massachusetts side-wall vent co detector requirements: step by step
- Confirm hard-wired CO detector with battery backup on the installation floor level.
- Confirm CO detectors with alarms on each additional level.
- Confirm the 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' sign is installed 8 ft above grade.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.