Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Live circuits and service safety

Viessmann · Versatronik 511 and 511D

More than one circuit is live. Shut off power to the control and the damper/blower before servicing, because contact with live parts can cause serious injury or death. Follow the wiring diagram in the manual.

  1. Turn off power to the control.
  2. Turn off power to the damper/blower.
  3. Confirm the circuits are dead before touching wiring.

Locate the cascade control programming unit and default display

Viessmann · Multi boiler cascade system, Vitotronic 300-K MW2C

All settings for the heating system are changed centrally at the Vitotronic 300-K. Each boiler has its own Vitotronic 200 control unit, which is limited in display and settings.

  1. If the screensaver is active, tap the display anywhere to start.
  2. To return to the default display from anywhere in the menu, tap the home button in the footer.
  3. The default display lists the boilers in boiler sequence order. The sequence can be changed on page 21.

Locating the serial number for parts orders

Viessmann · Vitodens 200-W B2HB, all models

Parts orders need either the 16-digit boiler serial number on the bar code label or the 12-digit ASME/NB serial number. Both are under the front enclosure panel. Remove the panel first.

  1. Remove the front enclosure panel (see page 15 of the manual).
  2. Read the 16-digit serial from the bar code label or the 12-digit ASME/NB serial.
  3. Give the serial when ordering parts, because some parts are not reverse compatible with earlier versions.

LON communication module is pre-installed

Viessmann · Vitocrossal 300 CU3A 26 to 199

The boiler comes with a LON communication module already fitted. Refer to the Service Instructions and the Vitotronic 200-H HK1B installation instructions for LON wiring.

LON communication wiring

Viessmann · Multiple control units on LON

A LON module on the control unit allows data transfer between units. Interruption of communication is shown on the unit.

  1. Connect the control units with the LON connecting cable.
  2. Fit a terminal resistor on the first and last control unit only.
  3. Watch for the communication interruption indicator if data stops.

Long shutdown (e.g. after heating season)

Viessmann · Vitocrossal 300 CA3B Dual Fuel boiler

Clean the boiler before a long shutdown to prevent corrosion. The heating system can stay filled and pressurized.

  1. Clean the combustion chamber, the flue gas collector and the vent pipe.
  2. Remove remaining condensate from the flue gas collector through the inspection opening.
  3. Leave the heating system filled and under pressure if desired.

Long shutdown cleaning

Viessmann · Vitocrossal 200 CM2 186 to 620

After a long shutdown, such as after the heating season, the combustion chamber, flue gas collector and vent pipe should be cleaned to prevent corrosion. The system can stay filled and pressurized.

  1. Clean the combustion chamber, flue gas collector and vent pipe.
  2. Remove remaining condensate from the flue gas collector through the front inspection service opening.

Long shutdown of boiler

Viessmann · Vitocrossal 300 CA3B

After an extended shutdown, for example after the heating season, the boiler must be cleaned to prevent corrosion. The heating system can stay filled and pressurized.

  1. Properly clean the combustion chamber, flue gas collector and vent pipe.
  2. Remove remaining condensate from the flue gas collector through the inspection opening.

Long shutdown preparation

Viessmann · Vitocrossal 300 CA3B

After a long shutdown, such as at the end of the heating season, clean the combustion chamber, flue gas collector and vent pipe to prevent corrosion. The system can stay filled and pressurized.

  1. Clean the combustion chamber, flue gas collector and vent pipe.
  2. Remove remaining condensate from the flue gas collector through the inspection opening.
  3. Leave the system filled and under pressure if desired.

Low water cut-off (LWCO) installation

Viessmann · Vitorond 200 VD2A boiler

A low water cut-off must be installed when the boiler sits above radiation level. It must be an approved type and is standard equipment. The mechanical contractor installs it where local codes require. Viessmann recommends an LWCO in all installations.

  1. Install supply and return headers with pressure gauge, temperature gauge, air vent, LWCO, boiler drain valve and bypass pump.
  2. Pipe up to the isolation valves and close them before testing.

Low water cut-off and field-verified piping

Viessmann · Vitodens 200-W B2HB

Piping examples are simplified conceptual drawings. Piping and required components must be verified in the field. A low water cut-off (LWCO) is required where local codes call for it. Proper installation and function are the heating contractor's responsibility.

  1. Field-verify all piping and components against the drawings.
  2. Install a low water cut-off where local codes require it.

Low water cut-off and isolation valve

Viessmann · Vitodens 200-W B2HB with field-supplied remote low water cut-off

A remote-mounted low water cut-off may be required by local code. Do not place an isolation valve between the boiler and the low water cut-off. Follow the cut-off maker's installation instructions and the wiring diagram referenced in the manual.

  1. Check local code to see whether a low water cut-off is required.
  2. Mount the low water cut-off remotely, following the manufacturer's instructions.
  3. Do not install an isolation valve between the boiler and the low water cut-off.
  4. Wire the low water cut-off as shown in the applicable wiring diagram.

Low water cut-off installation

Viessmann · Low water cut-off

A low water cut-off may be required by local codes. It must be installed whenever the boiler sits above the radiation level.

  1. Use an approved type low water cut-off supplied by the heating contractor.
  2. Do not install an isolation valve between the boiler and the low water cut-off.
  3. Hydrostat 3250-Plus includes a low water cut-off with electro well sensor. Do not disable it, since local codes may require it.
  4. The 3250-Plus can be set to automatic (default) or manual reset.

Main component locations (legend)

Viessmann · Vitotron 100 VLN2

Numbered components on the general view: 1 heating element power supply terminals, 2 control panel, 3 pump, 4 pressure relief valve, 5 pressure sensor, 6 magnetic filter, 7 manual reset high limit device, 8 heating element, 9 flow and outlet temperature sensor, 10 by-pass valve, 11 water inlet, 12 water outlet.

Main menu layout

Viessmann · Vitocrossal 200 CI2 control unit

The main menu holds all control unit settings. Menus are Heating, Test mode (contractors only), DHW, Settings, Information, Holiday program, Message lists and Service (contractors only).

  1. From the home screen, tap the menu button to open the main menu.
  2. From anywhere in the menu, tap the home button and then the menu button to return to the main menu.
  3. Use Information to check the set operating program, and Message lists for pending messages.

Main menu overview

Viessmann · Vitotrol 300A

The main menu lists the adjustable items. The extended menu is described on page 11 of the manual, which is not in this extract.

  1. Setback mode
  2. DHW set point temp
  3. DHW schedule
  4. DHW recirc pump sched
  5. Room set point temp
  6. Set room temp setpoint
  7. Heating schedule
  8. Vacation schedule

Main menu readouts available to the technician

Viessmann · Vitocrossal 200 CI2 Main menu > Information

The Main menu Information section gives read-only values for the boiler, heating circuits, DHW and network. Items include outside and supply temperatures, flue gas temperature, burner hours and starts, thermal output, central fault message, diverter valve position, boiler and HMU serial numbers, OEM software number, safety function status, altitude, pump status, heating curve slope and level, operating program and status, and network data such as MAC address, IP settings and backend connection. Additional heating circuits show the same values as heating circuit 1.

  1. Open the Main menu and go to Information.
  2. Check the required value (for example flue gas temperature, burner starts or central fault message).
  3. Use the Information values to confirm the boiler serial number and OEM software number before ordering parts or calling support.

Main PCB LV connection legend

Viessmann · Main PCB LV

Legend for the low-voltage main board. It covers the outside temperature sensor, the common supply sensor, the DHW tank sensors (1 and optional 2), the primary store sensor, the external hook-ups, the optional KM BUS participant and the LON cable between control units. The wiring drawing itself is not on these pages.

Main power supply terminal wire colours

Viessmann · Main power supply connection

The main power terminals are push-in type and accept only one conductor each.

  1. Connect the grey wire to Line (L).
  2. Connect the blue wire to Neutral (N).
  3. Connect the green/yellow wire to Ground (G).
  4. Press the orange button to open the terminal before inserting or releasing a wire.
  5. See page 31 of the manual for power supply connection details.

Maintenance and energy saving

Viessmann · Vitotronic 200-H, Model HK1M

Regular maintenance keeps heating trouble-free and efficient. The manual recommends an inspection and maintenance contract. Energy saving measures include ventilating briefly with windows fully open and radiator valves closed, keeping room temperature near 20 °C (each degree lower saves up to 6%), closing roller shutters at dusk, not covering radiators or valves, and alternating normal and reduced room temperature.

  1. Arrange an inspection and maintenance contract with the heating contractor.
  2. Ventilate briefly with windows fully open and radiator valves closed.
  3. Keep room temperature near 20 °C.
  4. Close roller shutters at dusk.
  5. Do not cover radiators or thermostatic valves.
  6. Use normal and reduced room temperature settings on the control unit.

Manual sequence for cascade stages

Viessmann · Cascades in Service operation mode

In service mode the cascade boilers can be started one stage at a time. For a second stage on multi-stage units, preset an output above 50%. Entries reset automatically when service functions close.

  1. Open the Manual Sequence level (service code required).
  2. Select the heat generator with the F button.
  3. Select the output for that boiler.
  4. For a multi-stage unit, set the output above 50% to start the second stage.

Manually adjust the mixing valve motor

Viessmann · Mixing valve motor

Use this to move the valve by hand when the motor is out of service.

  1. Lift the motorized lever up.
  2. Unhook the mixing valve handle.
  3. Remove plug A from the motor.
  4. For 24 V actuators, follow the instructions supplied with the actuator.

Marine or damp coastal installations

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Metal casing and fan housing corrode quickly in damp, salty air. Boilers in these areas must not use direct vent systems that draw outdoor air.

  1. Install room air dependent venting in marine environments.
  2. Keep indoor relative humidity low, for example avoid frequent laundry drying in the room.

Marine or damp salty environment venting

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

In damp, salty coastal areas chloride from sea spray can corrode the casing and fan housing. Boilers in these areas must use a room-air-dependent vent system, not a direct vent that draws outdoor air.

  1. Identify if the install is in a damp, salty coastal area.
  2. Use a room-air-dependent vent system, not a direct vent system.

Marine or damp salty environments

Viessmann · Vitodens 200-W B2HA 19, 28, 35

In coastal or marine areas, salt spray and humidity corrode the casing and fan housing. Do not use direct vent systems that pull outdoor air. Use a room air dependent vent system so the indoor air stays drier.

Marine or salt-air installations

Viessmann · Coastal installations

Direct vent air intake is not acceptable in damp, salty coastal areas. Use room air dependent venting.

  1. Do not use direct vent systems in marine environments.
  2. Install with a room air dependent vent system.

Massachusetts CO detector and signage requirements

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

For side-wall horizontally vented installs in Massachusetts where the vent terminal is under 7 ft above grade, a hard-wired CO detector with battery backup is required on the gas equipment floor and an alarm on each additional level. A metal or plastic sign reading 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' is required at least 8 ft above grade in line with the vent. Certain equipment is exempt.

  1. Confirm a hard-wired CO detector with battery backup is on the gas equipment floor.
  2. Confirm a CO detector with alarm is on each additional level served.
  3. Confirm the warning sign is posted at least 8 ft above grade, in line with the vent terminal.

Massachusetts CO detector and signage rules for sidewall vented installations

Viessmann · Sidewall horizontally vented fuel equipment in Massachusetts

For sidewall horizontally vented gas equipment in Massachusetts residential buildings where the vent termination is under 7 ft above grade, hard-wired CO detectors with alarm and battery backup are required on the floor level of the installation, with alarms on each additional level. Signage is required at the vent.

  1. Confirm a hard-wired CO detector with battery backup is on the installation floor level.
  2. Confirm CO detectors with alarms are on each additional level served.
  3. If the requirements cannot be met at completion, install a battery operated CO detector and allow 30 days to comply.
  4. Detectors must meet NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
  5. Mount a metal or plastic sign at least 8 ft above grade in line with the vent terminal reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.

Massachusetts side-wall vent CO detector requirements

Viessmann · Installations in the Commonwealth of Massachusetts

For side-wall horizontal venting where the vent end is under 7 ft above grade, a hard-wired CO detector with battery backup must be on the floor level of the installation, and CO detectors with alarms on each additional level. A warning sign must be placed 8 ft above grade in line with the vent.

  1. Confirm hard-wired CO detector with battery backup on the installation floor level.
  2. Confirm CO detectors with alarms on each additional level.
  3. Confirm the 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' sign is installed 8 ft above grade.

Massachusetts side-wall vent requirements

Viessmann · Installations in the Commonwealth of Massachusetts

For side-wall horizontally vented gas equipment in Massachusetts dwellings where the vent termination is under 7 ft above grade, a hard-wired CO detector with battery backup is required on the installation floor level and CO detectors on each additional level. A warning sign is also required 8 ft above grade in line with the vent. A 30-day allowance applies only if a battery CO detector is installed meanwhile. Detectors must meet NFPA 720 and ANSI/UL 2034.

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.