Viessmann Boiler: Manual sequence for cascade stages
Manual sequence for cascade stages on a Viessmann boiler: In service mode the cascade boilers can be started one stage at a time. For a second stage on multi-stage units, preset an output above 50%. Entries reset automatically when service functions close.
Applies to: Cascades in Service operation mode
How to fix manual sequence for cascade stages: step by step
- Open the Manual Sequence level (service code required).
- Select the heat generator with the F button.
- Select the output for that boiler.
- For a multi-stage unit, set the output above 50% to start the second stage.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 200 installation and operating manual, p. 164. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.