Viessmann Boiler: LON communication setup notes
LON communication setup notes on a Viessmann boiler: The LON communication module is an accessory and must be plugged in. Data transfer over LON can take several minutes. In one LON system no participant number may be used twice.
Applies to: Vitotronic 300-K and 200-H
How to fix lon communication setup notes: step by step
- Fit the LON communication module (see parts list).
- In code 1, set the LON participant number at coding address 77.
- Allow several minutes for LON data transfer before judging the system.
- Make sure each participant number is unique on the LON.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200-H
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
More commissioning tips for boiler
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.