Commissioning: Boiler tips (part 12 of 21)
Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.
Installation requirements for side-wall horizontal venting in Massachusetts
Viessmann · Side-wall horizontally vented gas equipment, Commonwealth of Massachusetts
For side-wall horizontally vented gas equipment in Massachusetts dwellings where the vent termination is under 7 feet above grade, a hard-wired CO detector with battery backup is required on the installation floor, and a battery-operated or hard-wired CO detector on each additional level. A metal or plastic sign reading 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' must be mounted at least 8 feet above grade in line with the vent terminal. The detectors must meet NFPA 720 and ANSI/UL 2034 with IAS certification.
- Confirm a hard-wired CO detector with battery backup is on the installation floor.
- Confirm battery-operated or hard-wired CO detectors are on each additional level.
- If the requirement cannot be met at completion, install a battery-operated CO detector and comply within 30 days.
- Mount the required sign at least 8 feet above grade, in line with the vent terminal.
Installing insulation and jacket panels
Viessmann · Vitorond 100 VR1 boilers
Insulation blankets and panels are fitted around the cast iron block. Fit the Vitotronic cable and panels in the order shown in the manual.
- Wrap the insulation blanket around the cast iron block with the cutout facing front, and secure it with the spring clips.
- If installing a Vitotronic control, run the plug-in connector cable down behind the front panel and out the bottom.
- Install support brackets and the left side panel, line up the bottom tab with the casting leg notch, and bend the tab down.
- Install the rear insulation blanket with the black side facing out, then install the rear panel.
- Install the right side panel on the brackets, with its top over the rear panel, and bend down the bottom tab.
- Before installing the top panels, follow the Vitotronic sections if a control is fitted.
- Slide the top front panel locking notches into the side panel holes, then install the top rear panel.
- Secure the top rear panel with sheet metal screws and mount the front panel with screws.
Installing the safety devices (pressure relief and drain valve)
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Use the factory supplied approved pressure relief valve. Relief valve and fittings are 3/4 in. NPT minimum. Do not install an isolation valve between the boiler and the relief valve, and do not install a shutoff valve or reduce the diameter in the discharge pipe. The discharge pipe must not be threaded at the end, must run close to a floor drain and end about 6 in. (150 mm) above it, and must never be piped outdoors. Orient the discharge to prevent scalding. Piping to a precharged expansion tank is field supplied.
- Remove the loosely pre-assembled combination pressure relief and drain valve assembly.
- Apply pipe sealant to both ends of fittings B, D, F and H, and install them onto tees A and E.
- Install the pressure relief valve G and the isolation valve C on the tees, and tighten.
- Run the discharge pipe to a floor drain, ending about 6 in. (150 mm) above the drain, with no threads on the end.
- Confirm there is no shutoff valve in the discharge pipe and the pipe is not reduced in size.
- Confirm the relief valve and discharge pipe are at least 3/4 in.
Instruct the system owner
Viessmann · Vitorond 200 VD2 boilers
Explain system operation sequence, start-up and shutdown, and the need for combustion air. Demonstrate an emergency shutdown and what to avoid. Explain that proper maintenance is required for safe operation.
Instructing the system user
Viessmann · System handover
The installer must give the operator the operating instructions for the system and all accessories, such as remote controls, and explain required maintenance.
- Hand over operating instructions for the system and any accessories.
- Train the operator on system operation and maintenance requirements.
Isolation and drain valves for service
Viessmann · Vitocrossal 200 CI2 399 to 2000
Install boiler isolation valves on the system supply and return, with drain valves above them. This allows boiler or system maintenance without draining the whole system. The boiler suits only closed hot water heating systems with pumps.
- Install isolation valves on the system supply and return.
- Install drain valves above the isolation valves.
- Use the boiler only on closed hot water systems that use pumps.
Jumper between the 40A plug and 157 plug
Viessmann · Application 5 (VD2T 2HC2T2ZP.02)
Application 5 requires a jumper between the 40A plug and the 157 plug.
- Install the jumper between the 40A plug and the 157 plug before starting up Application 5.
Jumper pin must be removed for on-demand DHW via CombiPLUS
Viessmann · Vitodens 100-W WB1B with CombiPLUS
If the X8 jumper pin is left in place, the boiler will not provide on-demand hot water through the CombiPLUS. If the jumper is removed but the CombiPLUS is not programmed, DHW falls back to the built-in resistors in the power pump module.
- Remove the X8 jumper pin.
- Program the boiler for CombiPLUS use (see programming, p. 35).
Keep sensor and remote wiring away from line voltage
Viessmann · Sensor and remote control wiring
Sensor and remote control wiring can pick up electromagnetic interference. Keep it away from 120/240 VAC conductors and use shielded or twisted pair where crossings cannot be avoided.
- Route low voltage sensor wiring away from 120/240 VAC conductors.
- If crossing cannot be avoided, use stranded twisted pair or shielded wire.
- Ground only one end of the shielding.
Keep sensor cables and capillaries clear of the heat exchanger
Viessmann · Sensor cables and capillaries on Vitotronic control
Do not kink capillaries, or sensors will not read correctly. Route all cables and capillaries between the nylon-backed insulation and the metal panels, never directly on the cast iron heat exchanger.
Lago FB remote heating circuit control (accessory)
Viessmann · Lago FB remote with Versatronik 200
Lago FB remote controls mixing valve circuit 1 and/or 2 over CAN bus. It mounts on a wall sub-base with a wiring strip. It has a room temperature trim of ±5 K and an integrated room sensor. Two Lago remotes can be wired in parallel.
- Secure the sub-base to the wall with field-supplied hardware.
- Connect the sub-base with 4-conductor cable: H to terminal 1, L to terminal 2, — to terminal 3, + to terminal 4.
- For a second Lago, parallel the terminal connections.
Language and display at first start
Viessmann · Start-up wizard
The display starts in German at commissioning and must be changed to the required language.
- Select the language option on the first wizard screen.
- Choose the required language.
- Press OK to accept.
Lead boiler activation contact must stay closed
Viessmann · Multi-boiler systems
On multi-boiler systems the boiler activation contact is essential and the lead boiler contact must be constantly closed.
- Verify the lead boiler activation contact is closed during operation.
Lead boiler activation contact on multi-boiler systems
Viessmann · Multi-boiler systems
The boiler activation contact is essential on multi-boiler systems and must not be left open on the lead boiler.
- Verify the contact on the lead boiler is constantly closed before startup.
Leak test the gas supply before start-up
Viessmann · Vitodens 100-W WB1B
The gas supply piping must be leak tested before the boiler goes into operation. Check all gas joints and valves under normal operating pressure with an approved leak detection liquid, never with an open flame.
- Leak test all gas joints under normal operating pressure with approved leak detection liquid.
- Confirm the gas valves do not leak.
- Do not use an open flame to check for leaks.
Leave the rotary address dial at 0
Viessmann · Versatronik 515 and 515D gateways
The rotary dial sets LON addressing. Leave it at the factory default of 0 unless several gateways are on the same system, where a unique setting is needed to avoid duplicate LON addresses.
- Check that the rotary dial is at 0.
- Change the dial only on systems with multiple 515 gateways, and give each gateway a unique setting.
Level the boiler for condensate drainage
Viessmann · Vitodens 200-W B2HA 45, 60
The boiler must sit level both vertically and horizontally or condensate will not drain properly.
- Use the levelling screws to level the boiler front to back and side to side.
- Check the level again after the connections are made.
Licensed installer and annual service
Viessmann · Boiler and control system
Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor. The contractor must train the owner on the system, shutdown procedure and the need for annual professional service before the heating season.
- Confirm the installer is a licensed professional heating contractor.
- Check that the owner has been shown the shutdown procedure.
- Arrange annual professional service before each heating season.
Locate disconnect and gas shut-off outside the mechanical room
Viessmann · Vitocrossal 300 CA3B Dual Fuel
Viessmann recommends a separate electrical disconnect and, where possible, a fuel shut-off valve installed outside the mechanical room or enclosed installation area.
- Install an extra electrical disconnect outside the mechanical room.
- Install a fuel shut-off valve outside the room if possible.
LON bus wiring length and participant limits
Viessmann · Vitotronic 300-K and Vitotronic 200-H on LON system
Up to 99 participants can share the LON bus. Maximum line length is 3000 ft (900 m) with LON plugs, or 3000 ft (900 m) when using LON junction boxes with a 23 ft (7 m) LON cable. A terminator is required at the end of the bus.
- Connect the control unit or Vitocom as the start of the bus.
- Use on-site cable with LON plugs, or LON cable with junction boxes, as shown in the manual.
- Fit a terminator at the far end of the line.
- Keep the total line length within 3000 ft (900 m).
LON communication setup notes
Viessmann · Vitotronic 300-K and 200-H
The LON communication module is an accessory and must be plugged in. Data transfer over LON can take several minutes. In one LON system no participant number may be used twice.
- Fit the LON communication module (see parts list).
- In code 1, set the LON participant number at coding address 77.
- Allow several minutes for LON data transfer before judging the system.
- Make sure each participant number is unique on the LON.
LON setup notes
Viessmann · Vitodens 200-W B2HA 112–530
Data transfer over LON can take several minutes.
- Install the LON communication module (accessory) per its installation instructions.
- Set participant numbers and functions via coding level 2.
- Assign unique participant numbers.
- Program only one Vitotronic as fault manager.
Low water cut-off
Viessmann · Vitodens 222-F, B2TB
A low water cut-off may be required by local codes.
- Check local codes for a low water cut-off requirement.
- Do not install an isolation valve between the boiler and the low water cut-off.
Low water cut-off (LWCO) device connection
Viessmann · Vitotronic 200 KW2 with low water cut-off
A 3-conductor cable runs from the low water cut-off to the Power Pump Module. The LWCO contact closes when water is present. The jumper on the Power Pump Module board must be removed when an LWCO is installed.
- Run a 3-conductor cable between the LWCO device and the Power Pump Module.
- Remove the jumper between terminals L/P1 and P2 on the Power Pump Module board.
- Wire the LWCO as shown in the manual drawing.
- After installation, check that the LWCO function works.
Low water cut-off and isolation valves
Viessmann · Vitocrossal 300 CU3A installation
Low water cut-off requirements for the boiler.
- Install an approved low water cut-off if local codes require one, and always if the boiler is installed above the radiation level.
- Do not install an isolation valve between the boiler and the low water cut-off.
- Let the heating contractor supply the low water cut-off device.
Low water cut-off device
Viessmann · Vitodens 200-W B2HA 45, 60
A low water cut-off may be required by local code.
- If required, install an approved low water cut-off per its manufacturer instructions.
- Do not install an isolation valve between the boiler and the low water cut-off.
Low water cut-off device in every system layout
Viessmann · Vitotronic 300 KW3, all application examples
All five application examples show a low water cut-off device wired into the boiler system. Include it in any layout you build.
Low water cut-off placement
Viessmann · Vitodens 200-W B2HA 45, 60 system piping
A low water cut-off (LWCO) is required wherever local codes call for one. Piping and components must be verified in the field, and proper function is the responsibility of the heating contractor.
- Check local codes for LWCO requirements.
- Install the LWCO where required.
- Verify all piping and components in the field against the simplified layout drawings.
Low water cut-off requirement
Viessmann · Supply header
A low water cut-off is required if the boiler sits above radiation level. Viessmann recommends one in all installations.
- Install an approved low water cut-off in the supply header, by the mechanical contractor where local code requires it.
Low-loss header and pump sizing
Viessmann · Multi-circuit and high-flow systems
A low-loss header is strongly recommended when system flow may exceed boiler max flow or when flow is unknown. Field pump sizing is critical in underfloor systems.
- Check the system flow rate against the boiler maximum water flow rate table.
- Fit a low-loss header if flow may exceed the boiler maximum or flow is unknown.
- Size the field-supplied pump against the boiler supply head pressure drop to avoid short-cycling.
- Install a low water cut-off where local codes require it.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.