Viessmann Boiler: Ionization current acceptance limit
Ionization current acceptance limit on a Viessmann boiler: Minimum ionization current needed for a stable flame.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner
How to fix ionization current acceptance limit: step by step
- Confirm the ionization current reaches at least 3 µA for approx. 2 to 3 sec after the combination gas valve opens and while in operation.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.