Installing the safety devices (pressure relief and drain valve) on a Viessmann boiler: Use the factory supplied approved pressure relief valve. Relief valve and fittings are 3/4 in. NPT minimum. Do not install an isolation valve between the boiler and the relief valve, and do not install a shutoff valve or reduce the diameter in the discharge pipe. The discharge pipe must not be threaded at the end, must run close to a floor drain and end about 6 in. (150 mm) above it, and must never be piped outdoors. Orient the discharge to prevent scalding. Piping to a precharged expansion tank is field supplied.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

How to fix installing the safety devices (pressure relief and drain valve): step by step

  1. Remove the loosely pre-assembled combination pressure relief and drain valve assembly.
  2. Apply pipe sealant to both ends of fittings B, D, F and H, and install them onto tees A and E.
  3. Install the pressure relief valve G and the isolation valve C on the tees, and tighten.
  4. Run the discharge pipe to a floor drain, ending about 6 in. (150 mm) above the drain, with no threads on the end.
  5. Confirm there is no shutoff valve in the discharge pipe and the pipe is not reduced in size.
  6. Confirm the relief valve and discharge pipe are at least 3/4 in.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

More commissioning tips for boiler

Source: Vitodens 200-W B2HB installation manual, p. 29. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977