Viessmann Boiler: Ignition, gas leak test and CO measurement at startup
Ignition, gas leak test and CO measurement at startup on a Viessmann boiler: Gas leak checks and CO readings are required around any gas work. Startup faults from air in the gas line are common, especially with LPG.
Applies to: Vitodens 200-W B2HA 45, 60
How to fix ignition, gas leak test and co measurement at startup: step by step
- Take a CO measurement before and after working on the gas appliance (see page 27).
- Check for gas leaks with soap and water only. Do not use matches, candles or flame, and do not purge gas into the combustion chamber.
- Make sure there is no open flame in the room.
- If a fault shows during first startup because of air in the gas supply, wait about 5 seconds and press the R reset button. Ignition repeats.
- Record the combustion values in the order given in the Maintenance Record on page 96.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.