Commissioning: Boiler tips (part 11 of 21)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.

Hanging the boiler on the bracket

Viessmann · Vitodens 100-W B1HE and B1KE

Protective caps on connections stay on until the boiler is about to be fitted. The wooden blocks on the bottom rails must be removed after mounting.

  1. Hang the boiler on the wall bracket.
  2. Confirm all four mounting tabs have locked into the boiler.
  3. Remove the plastic shipping caps from the connections.
  4. Remove the wooden blocks from the bottom rails.

Heat demand inputs must be dry contacts

Viessmann · Application 4 (VD2T 2HC2T2ZP.01)

Heat demand from an air handler or an infloor control must be a potential-free dry contact. Do not apply line voltage to these inputs.

  1. Use a potential-free contact for air handler heat demand.
  2. Use a potential-free contact for the radiant circuit from a thermostat, zone valve or multi-zone controller.

Heating circuit assignment

Viessmann · Two-circuit Vitotronic 200 KW2 systems

On systems with two heating circuits, select the circuit before making settings, because settings apply to the selected circuit.

  1. Confirm labels show Heating circuit 1 without mixing valve and Heating circuit 2 with mixing valve.
  2. Press the circuit button for the circuit to set. The corresponding button lights.

Heating circuit controls not on LON bus

Viessmann · Circuit diagrams 3, 4 and 5

When downstream heating circuit controls are not connected to the boiler control unit via LON, the temperature sensor and plug wiring must match the coding.

  1. Wire temperature sensor T1 or T2 to plug aJA or aJB as shown in the circuit diagram.
  2. Set the matching coding (4A: 1 or 4b: 1 is set automatically when the sensor is connected).
  3. If sensor T1 closes the downstream mixing valves, set 4C: 2 and use plug sÖ (A1).

Heating circuit numbering (BUS ID 1/2)

Viessmann · Versatronik 200 system control, start-up settings

Heating circuits are numbered in sequence starting at 01. Never give two circuits the same number. When replacing a controller, enter the exact same heating circuit numbers as the old one. Sensor type (1 kOhm or 5 kOhm) is chosen during programming and system selection.

  1. Number heating circuits in sequence starting at 01.
  2. Check that no heating circuit number is used twice on the bus.
  3. On a replacement controller, enter the same heating circuit numbers as the unit it replaces.
  4. Set the sensor type (1 kOhm or 5 kOhm) to match the system selection made during programming.

Heating system layout and mixing valves

Viessmann · Vitodens 222-F, B2TB 68 and 125

Recommended maximum boiler supply temperature is 158°F (70°C) for heating and DHW to limit distribution losses. Avoid mixing valves on the heating circuit where possible because condensing boilers need low return temperatures. If a mixing valve is needed (multi-zone or underfloor), use only 3-way mixing valves. Never use 4-way mixing valves with condensing boilers. Underfloor systems and large-volume loops must connect through a 3-way mixing valve.

  1. Set max boiler supply temperature to 158°F (70°C) where possible.
  2. Avoid mixing valves on the heating circuit when possible.
  3. Use 3-way mixing valves only.
  4. Do not use 4-way mixing valves.

Heating system type sets the curve

Viessmann · Heating curve adjustment

Match the heating curve slope to the emitter type: low temperature for radiant floor, medium for cast iron or staple-up radiant, high for fintube or fan coils. The room set-point and outdoor temperature drive the curve.

  1. Identify the heat emitter type in the building.
  2. Set the slope and shift to match the building's required supply temperature.
  3. Check room temperature after the system has settled.

High altitude de-rate

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199 at 10,000 ft

At high altitude installation at 10,000 ft the input of models B2HB 45, 57, 160 and 199 is de-rated by 21 percent.

  1. Apply the 21 percent input de-rate when the boiler is installed at 10,000 ft altitude.

High altitude operation

Viessmann · Vitodens 200-W B2HB

The boiler can run at high altitude up to 10,000 ft (3,000 m) with a simple electronic adjustment. At 10,000 ft the input for B2HB 19 to 199 is derated by 21%.

  1. Set the high altitude adjustment electronically for the install site elevation.
  2. Account for the 21% input derate at 10,000 ft when checking input rate.

High gas supply pressure

Viessmann · B2HA 112, 150, 399, 530

Maximum gas supply pressure is 14 in. w.c. for both natural gas and LPG. If the supply can go above this, a separate gas pressure regulator must go upstream of the heating system.

  1. Measure the incoming gas supply pressure.
  2. If it can exceed 14 in. w.c., install a separate gas pressure regulator upstream of the boiler.
  3. Confirm the minimum pressure is 4 in. w.c. for natural gas or 10 in. w.c. for LPG.

High limit and air purge notes

Viessmann · Vitorond 100 VR1 with Hydrostat 3250-Plus

The Hydrostat high limit maximum setting is 240 F (110 C). A flow switch is not required on this boiler. Air must be bled from the system supply air vents, so avoid restrictive piping where air could be trapped.

  1. Set the high limit no higher than 240 F (110 C).
  2. Do not install a flow switch on this boiler.
  3. Bleed air at the system supply air vents.
  4. Avoid restrictive piping that can trap air.

Hydraulic separation of boiler and system

Viessmann · Applications 3, 4 and 5

Closely spaced tees or a low-loss header separate the boiler and system flows so they do not affect each other.

  1. Install closely spaced tees or a low-loss header between boiler and system loops.
  2. Size the boiler circulator and flow per the sizing section (pages 13-15, not included here).

Hydraulically separate boiler and system flow

Viessmann · Applications 1 to 3

Separating the boiler loop from the system loop keeps their flows from affecting each other, since system flow may fall outside the boiler's recommended range. A low loss header with a sensor improves control and efficiency.

  1. Use closely spaced tees or a low loss header between the boiler and system loops.
  2. Install a low loss header sensor if a header is used, for better control and efficiency.
  3. Check boiler flow sizing against the pressure drop chart referenced in the manual.

Hydrostatic pressure test before connecting the boiler

Viessmann · Vitorond 200 VD2A boiler

Leak test and hydrostatically pressure test the boiler before it is connected to piping or power. Hold between 127 psig (875 kPa) and 130 psig (896 kPa) maximum. Stay with the boiler during the test.

  1. Pipe up to the isolation valves and close them.
  2. Install temporary caps on the nipples for the pressure relief valve and expansion tank.
  3. Connect a hose to the boiler drain valve and fill slowly until the gauge reads 130 psig (896 kPa) max.
  4. Hold pressure for 30 minutes and do not leave the boiler unattended.
  5. Check all push nipples and pipe connections with a flashlight for leaks. Place paper under the cast iron block to catch minor drips from the bottom push nipples.
  6. After 30 minutes, open the drain valve slowly to release pressure.
  7. Remove the caps and install the pressure relief valve and expansion tank immediately.

Hydrostatic test pressure limits

Viessmann · All VD2A models

Minimum test pressure is 127 psig (875 kPa). Maximum is 130 psig (896 kPa), which is also 1½ times the maximum operating pressure. Do not exceed 130 psig.

  1. Set the test between 127 and 130 psig and hold for 30 minutes.

Hygiene and DHW temperature advice

Viessmann · DHW systems

Keep DHW above 122 F (50 C) for hygiene. Larger systems or low-exchange systems should stay above 140 F (60 C). Warn the owner about the risk of hot outlets.

  1. Explain the DHW temperature settings and the scald risk at draw-off points to the system user.

Ignition and reset after air in gas line

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

The boiler uses direct spark ignition and starts after a safety time. On first start the gas line may contain air and the unit can show a fault.

  1. If a fault appears at initial start-up, wait about 5 seconds.
  2. Press the reset button R on the burner to reset.
  3. The ignition sequence repeats automatically.

Ignition, gas leak test and CO measurement at startup

Viessmann · Vitodens 200-W B2HA 45, 60

Gas leak checks and CO readings are required around any gas work. Startup faults from air in the gas line are common, especially with LPG.

  1. Take a CO measurement before and after working on the gas appliance (see page 27).
  2. Check for gas leaks with soap and water only. Do not use matches, candles or flame, and do not purge gas into the combustion chamber.
  3. Make sure there is no open flame in the room.
  4. If a fault shows during first startup because of air in the gas supply, wait about 5 seconds and press the R reset button. Ignition repeats.
  5. Record the combustion values in the order given in the Maintenance Record on page 96.

Initial control unit start-up and settings

Viessmann · CA3B Series 2.5 to 6.0

The control unit comes pre-set, but several codings must be set on site. The cascade (lead boiler) control unit runs the system and boiler section 1, and the other units run as lag boilers.

  1. Switch on the main switch and all network switches on the control units.
  2. Switch on the control unit. Start-up runs automatically.
  3. Set the language, date and time, temperature units, system layout and elevation as needed.
  4. Confirm. The prompt 'Do you want to make further changes' appears.

Initial power-up of the control units

Viessmann · CA3B Dual Fuel 2.5 to 6.0

The control units come pre-set, but several codings must still be set on site. Switch on the main switch and all network switches first, then the control unit switch. Start-up runs automatically. Check the language, date and time, temperature units, system layout and elevation, then confirm with OK.

  1. Switch on the main switch and all network switches on the control units.
  2. Switch on the control unit; start-up begins automatically.
  3. Check language, date and time, temperature units, system layout and elevation.
  4. Confirm with OK, then answer the prompt 'Do you want to make further changes'.
  5. Check all addresses in coding level 1 and adjust as required.
  6. Check the listed coding addresses in coding level 2 and adjust.

Initial start-up and factory calibration

Viessmann · All B2HA models

Initial start-up must be done by a qualified heating contractor, who must also complete the Maintenance Record. The boiler is factory tested and calibrated, so gas valve adjustments are normally not needed at field start-up.

  1. Complete initial start-up as a qualified heating contractor.
  2. Fill in the Maintenance Record in the Service Instructions.
  3. Do not adjust the gas valve unless the situation requires it.

Initial start-up and handover

Viessmann · Vitodens 200-W B2HA 112/150/399/530

Initial start-up must be done by a qualified heating contractor. Complete the Maintenance Record, and show the owner the system operation, the emergency shutdown, and the need for yearly professional service.

  1. Perform initial start-up as a qualified heating contractor.
  2. Complete the Maintenance Record.
  3. Explain normal operation and emergency shutdown to the owner, including what to do and what not to do.
  4. Tell the owner that yearly professional maintenance is required.

Initial start-up and maintenance record

Viessmann · Vitocrossal 200 CI2

Initial start-up must be done by a qualified heating contractor, who also completes the maintenance record.

  1. Complete the Maintenance Record at initial start-up.
  2. Find the Maintenance Record on page 95 of the manual.
  3. Verify the field supplied controls, such as low water cut-offs, pumps, motorized valves, air vents and thermostats.

Initial start-up and matching done by heating contractor

Viessmann · Vitotronic 200-H HK1M

The first start-up and adjustment of the control to the local system and building must be carried out by the licensed heating contractor.

Initial start-up requirements

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

Initial start-up must be done by a qualified heating contractor. The Maintenance Record in the service instructions must be completed. Turn off main power and close the main gas valve before service work.

  1. Deactivate main power to the equipment, heating system and external controls.
  2. Close the main gas supply valve.
  3. Complete the Maintenance Record after start-up.

Install a carbon monoxide alarm

Viessmann · Vitocrossal 300 CU3A 26 to 199

Install at least one carbon monoxide alarm in the residential living space before the boiler is put into operation.

  1. Install at least one CO alarm in the living space.
  2. Follow the alarm maker's instructions and local codes.

Install CO alarm before startup

Viessmann · Vitodens 200-W B2HA 112/150/399/530

Confirm a carbon monoxide alarm is installed in the living space following the alarm maker's instructions and local codes before the boiler is put into operation.

  1. Check that a CO alarm is installed in the living space.
  2. Confirm it was installed per the manufacturer's instructions and local code before firing the boiler.

Install pressure relief valve and discharge piping

Viessmann · Vitodens 200-W B2HB 19, 26, 35, 68, 94, 125

Fit the factory pressure relief valve and drain valve with pipe sealant. The discharge pipe must go to a floor drain, not outdoors, and must not have a shutoff valve.

  1. Remove the pressure relief valve, drain valve and fittings from the box.
  2. Apply pipe sealant to both ends of the fittings and install the tees.
  3. Install the pressure relief valve and the isolation valve, then tighten them.
  4. Pipe the discharge to a floor drain, ending about 6 in. (150 mm) above the drain.
  5. Use an unthreaded pipe end, and make sure there is no shutoff valve in the discharge line.
  6. Do not install an isolation valve between the boiler and the pressure relief valve.
  7. Position the discharge so it cannot scald people.

Install the pressure relief valve and discharge pipe

Viessmann · Vitodens 200-W B2HA 80-100, 285-352

Use the factory supplied approved pressure relief valve. Do not put an isolation valve between the boiler and the relief valve. The discharge pipe must be unthreaded, not reduced, and free of shutoff valves, and must run to a floor drain. Never pipe the discharge outdoors.

  1. Install the factory supplied pressure relief valve.
  2. Do not install an isolation valve between the boiler and the relief valve.
  3. Run the discharge pipe, unthreaded, to a floor drain and end it about 6 in. (150 mm) above the drain.
  4. Keep the discharge pipe diameter at least 3/4 in. and do not reduce it.
  5. Place the discharge so it does not scald people nearby.

Installation codes to follow

Viessmann · Vitorond 200 VD2A

Install gas boilers to CAN/CSA-B149.1 or B149.2 in Canada, or NFPA 54 / ANSI Z223.1 in the U.S. Install oil boilers to CSA B-139 in Canada or NFPA 31 in the U.S. Wire to CSA C22.1 Part 1 in Canada or NFPA 70 (NEC) in the U.S. Use the latest editions and local codes where they apply.

  1. Identify the fuel and country, then follow the matching gas, oil and electrical code.
  2. Use the latest code editions and local amendments.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.