Viessmann Boiler: Hydronic flow and pipe head estimate
Hydronic flow and pipe head estimate on a Viessmann boiler: Flow and heat rate formulas and a quick pipe resistance estimate for sizing a circuit pump.
Applies to: Circulator and pipe sizing
How to fix hydronic flow and pipe head estimate: step by step
- Flow (GPM) = BTUH / (500 x ΔT).
- Heat rate (BTUH) = GPM x 500 x ΔT.
- For pipe resistance, measure the longest run of pipe.
- Add 50% for fittings.
- Multiply by 0.04 to get a rough feet of head the pump must overcome for that circuit.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: vitocrossal_300-cu3a_application_guide.pdf, p. 62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.