Other: Boiler tips (part 20 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Heating circuits M2 and M3 need an extension module
Viessmann · Vitotronic 200-H, type HK1B
The HK1B control unit can run up to 3 heating circuits, but only with the mixing valve extension module fitted. Heating circuits M2 and M3 need the heating circuit extension module, which is an optional accessory.
Heating curve and heating circuit terms
Viessmann · Vitotronic 300-K MW1B / Vitotronic 100 GC1B
Heating curves show the link between outside temperature, room temperature set value and supply temperature. The lower the outside temperature, the higher the boiler water or heating circuit supply temperature.
Heating operating modes
Viessmann · Heating operating mode setup
The boiler supplies heat at the set supply temperature. The contractor sets one of four operating modes at commissioning: weather-compensated, constant, or room temperature-dependent operation. Comfort, standard and reduced temperature levels are chosen by time program. In room temperature-dependent operation a separate room sensor is required, and the output does not follow outside temperature. Weather-compensated operation can run several heating circuits, and remote units can adjust settings. Constant operation holds a fixed supply temperature regardless of outside temperature.
Heating program changed by external control
Viessmann · Vitotronic 200-H HK1S/HK3S
Shows Ext. control when an external control has switched the heating program set on the control unit.
Heating program options
Viessmann · Vitotrol 300A
The heating program sets whether the rooms are heated, whether DHW is made, or whether the system is shut down with frost protection.
- Heating and DHW: rooms are heated and DHW is provided (winter mode).
- Only DHW: DHW is provided, no central heating (summer mode).
- Standby mode: frost protection for the boiler and DHW tank is on; no central heating and no DHW heating.
- There is no program for central heating alone. For central heating only, use Heating and DHW and set the DHW temperature to 50 F (10 C) so the tank is only kept from freezing (see p. 23).
Heating program: Heating vs Standby
Viessmann · Vitotronic 200 heating program setting
The heating program decides whether the boiler supplies heat to the Vitotronic 300-K MW2C or sits in standby with frost protection active. Two programs exist: Heating (boiler available for heat production) and Standby mode (frost protection only).
Heating programs and what they do
Viessmann · Vitotronic 200 and 300-K heating program
The heating program decides whether the system heats rooms and DHW, DHW only, or stays in standby with frost protection. Winter mode is 'Heating and DHW'. Summer mode is 'Only DHW', where the boiler still makes DHW but no central heating. 'Standby mode' turns off central heating and DHW but keeps frost protection active for the boiler and DHW tank. There is no heating-only program. For heating without DHW demand, select 'Heating and DHW' and set the DHW temperature to 10 °C (50 °F). DHW is then not heated needlessly, and the DHW tank stays frost protected.
- Select 'Heating and DHW' for winter operation with rooms and DHW.
- Select 'Only DHW' for summer operation.
- Select 'Standby mode' to shut down heating and DHW while keeping frost protection.
- For central heating only, select 'Heating and DHW' and set the DHW temperature to 10 °C (50 °F).
Heating water quality requirements
Viessmann · Vitocrossal 300 CU3A 26 to 199
Deposits and corrosion increase with poor fill water. Water harder than the limit must be softened.
- Flush the whole heating system before filling.
- Use potable quality water only.
- Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
- Add heating system inhibitors or antifreeze only if they are suitable for heating systems and added manually.
Heating/cooling changeover valves
Viessmann · Heating/cooling application with hydrostat
In a combined heating and cooling application, valves v1 and v2 switch the boiler loop between seasons.
- Cooling season: close v1 and open v2.
- Heating season: close v2 and open v1.
- Label the valves v1 and v2.
High altitude de-ration
Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125
At 10,000 ft (3050 m) altitude, the input of all B2TB 19, 35, 68 and 125 models is de-rated by 21%.
- Account for the 21% input de-ration when checking input at high altitude.
High altitude input de-rate
Viessmann · Vitocrossal 300 CU3A installed at high altitude
At 10,000 ft. altitude the input of the Vitocrossal 300 CU3A is reduced by 18%.
- Account for the 18% input reduction when checking input at high altitude.
High altitude input de-ration
Viessmann · Vitocrossal 300 CU3A at high altitude
At 10,000 ft altitude the input for the Vitocrossal 300 CU3A is de-rated by 18 percent.
- Account for the 18 percent input de-ration when installing at 10,000 ft altitude.
High limit setting can only be changed by coding card
Viessmann · Vitocrossal 300 CA3B 2.5 to 6.0
The fixed high limit cut-out is preset at 210°F (99°C) and can only be changed by changing the coding card.
- Do not change the fixed high limit by other means.
- Refer to the control section of the installation instructions for the coding card procedure.
Holiday function use
Viessmann · Heating and hot water holiday function
Holiday mode stops heating for the set period. Stop it early with the program switch.
- Enter the first day of the holiday as the holiday start date, not the day of travel. Heating stops from this day.
- Enter the last day without heating as the holiday end date, not the day of return. The house should be warm and have hot water when you arrive.
- To end the holiday early, press the program switch.
Hot water operation without burner (BoB)
Viessmann · Versatronik 200 hot water generation
BoB is used for operation with solar energy, for example. The burner is only enabled when storage values drop below the set tolerance limit.
- Select BoB for hot water generation where solar or another source supplies the heat.
- Check that the tolerance limit is set so the burner starts only when needed.
Hot water pipe clearance to combustibles
Viessmann · Vitodens 200-W B2HB
Keep at least 2 in. (51 mm) circumferential clearance from non-insulated hot water pipes to combustible construction. With adequately insulated pipe, the clearance can drop to 0 in. where local gas codes allow.
- Keep 2 in. (51 mm) around non-insulated hot water pipes from combustible construction.
- With suitable pipe insulation, 0 in. is allowed only if local gas codes permit.
How heating curve adjustments change supply temperature
Viessmann · Heating curve settings
Changing the slope alters the gradient of the curve. Changing the shift moves the whole curve up or down in parallel. Changing the standard room temperature setpoint offsets the curve along the room temperature axis. The lower the outdoor temperature, the higher the boiler water or supply temperature.
How the heating curve works
Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352
The lower the outdoor temperature, the higher the boiler water or supply temperature. Room temperature follows boiler water temperature. A different room setpoint shifts the curve parallel. The boiler water is raised above the required supply temperature by a set differential (factory 14.4°F / 8 K, coding address 9F). The supply temperature cannot exceed the boiler water temperature. Heating curve slope suits system type: low temperature (radiant floor) 0.2 to 0.7; medium temperature (cast iron, panel radiant floor) 0.7 to 1.2; high temperature (fin tube, fan coils) 1.2 to 1.5.
Hydraulic example scheme reference
Viessmann · Vitocrossal 300 CU3A 26 to 199, example layout 1
Page 32 gives hydraulic scheme ID 4605300_1006_01 as a basic example only. It has no shut-off valves or safety equipment and does not replace local engineering.
- Add shut-off valves and safety equipment as required by local engineering.
Hydronic and electrical component index
Viessmann · Vitodens 222-F system piping and wiring
Components shown in the application drawings and the component index.
- Hydronic: ball valve, circulator with isolation flanges, low loss header, thermostatic mixing valve, radiant infloor manifold, motorized mixing valve, flow check valve, air eliminator, expansion tank, zone valve, hydronic air handler, plate and frame heat exchanger, purge assembly.
- Electrical: aquastat, secondary low water cut-off, outdoor temperature sensor, thermostat, temperature sensor, Vitotrol multi-zone control, 24V zone valve, 120 Volt circulator, 3-way mixing valve with actuator motor.
Hydronic flow and pipe head estimate
Viessmann · Circulator and pipe sizing
Flow and heat rate formulas and a quick pipe resistance estimate for sizing a circuit pump.
- Flow (GPM) = BTUH / (500 x ΔT).
- Heat rate (BTUH) = GPM x 500 x ΔT.
- For pipe resistance, measure the longest run of pipe.
- Add 50% for fittings.
- Multiply by 0.04 to get a rough feet of head the pump must overcome for that circuit.
Hydrostat thermal targeting
Viessmann · VR1 22 to 33, 91 to 140
The Fuel Smart Hydrostat watches thermostat activity. It raises the boiler target temperature in cold weather and lowers it in mild weather to save fuel.
Hydrostat thermal targeting behavior
Viessmann · Vitorond 100 with Fuel Smart HydroStat
Thermal Targeting analyzes thermostat activity and raises or lowers the boiler target temperature with heat demand. Colder outdoor conditions raise the target; milder conditions lower it to save fuel.
If you smell gas
Viessmann · Vitocrossal 300 CU3A, all models
Do not light any appliance and do not touch electrical switches or use a phone in the building. Call the gas supplier from a neighbour's phone and follow their instructions. If the gas supplier cannot be reached, call the fire department.
- Do not light any appliance.
- Do not touch electrical switches or use a phone in the building.
- Call the gas supplier from outside the building, from a neighbour's phone.
- If the gas supplier cannot be reached, call the fire department.
Indirect DHW tank service interval
Viessmann · Vitocrossal 300 CA3B with indirect DHW tank
Indirect-fired domestic hot water storage tanks need regular service.
- Service indirect-fired DHW storage tanks within two years of installation at the latest.
- Continue regular service after that.
Indirect DHW tank: flow check valves
Viessmann · Vitocrossal 200 CI2 399 to 2000
When the boiler heats an indirect DHW tank, heating loops without a mixing valve need flow check valves on the pump discharge side to stop reverse flow.
- Install flow check valves on the discharge side of the pumps in loops without a mixing valve.
Information scan list (lead control unit and boiler sections)
Viessmann · Vitocrossal 300 CA3B, lead control unit and boiler section 2 or 3
Scan list under Information. Some items only appear depending on equipment level. Items marked with an arrow can be opened for more detail.
- General: outdoor temp, boiler temperature, flue gas temperature, burner starts and hours, boiler sequence, sensors 9, 17A, 17B, outputs 20, 29, 52, feed pump, central fault message, participant no., time and date.
- Burner control: burner hours run, burner starts, max operational output, gas type, altitude, max boiler temperature, integral threshold controller, runtime optimization.
- Heating circuits 1 to 3: heating program, operating status, time program, room temperature targets, slope, shift, pump and mixing valve status, supply temperature, holiday program.
- Solar (if fitted): collector temp, solar energy, solar circuit pump status and hours, sensor 7 and 10, output 22.
- DHW: DHW time program, circulation time program, DHW temperature (top and bottom with two sensors), circulation pump, tank primary pump.
Information shown per fault
Viessmann · Vitodens 100-W B1HE/B1KE
Each fault shows the date and time, the fault code, a description, and the subscriber number of the affected component.
Initial checks before troubleshooting
Viessmann · Vitotronic 100 KW10B
Confirm the basics before working through the symptom guides.
- Confirm all controls operate properly (thermostats, low water cut-off, etc.).
- Confirm all wire connections are tight and secure.
Inlet damper must be fully open
Viessmann · CM2 246 and 311
If the burner inlet damper does not open fully, it can cause malfunctions or show that the servomotor is set up wrong.
- After any damper, servomotor or linkage work, confirm the damper vents are fully open.
- Adjust the linkage if the vents are not fully open.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.