Viessmann Boiler: High gas supply pressure

Updated · by Aurora Star Tech Inc.

High gas supply pressure on a Viessmann boiler: Maximum gas supply pressure is 14 in. w.c. for both natural gas and LPG. If the supply can go above this, a separate gas pressure regulator must go upstream of the heating system.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: B2HA 112, 150, 399, 530

How to fix high gas supply pressure: step by step

  1. Measure the incoming gas supply pressure.
  2. If it can exceed 14 in. w.c., install a separate gas pressure regulator upstream of the boiler.
  3. Confirm the minimum pressure is 4 in. w.c. for natural gas or 10 in. w.c. for LPG.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

More commissioning tips for boiler

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 103. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.