Viessmann Boiler: Heat generator bus scan after restart
Heat generator bus scan after restart on a Viessmann boiler: After a restart or new configuration the controller scans the bus for heat generators for about 1 minute. The display shows SCAN. Manual output entries are blocked during this time.
Applies to: Versatronik 200 cascade controller
How to fix heat generator bus scan after restart: step by step
- Wait for the SCAN to finish (about 1 min).
- Check the list of detected boilers. An X shows a heat generator that answered on the bus.
- Check each output value. If a heat generator gave no output, 15 kW is entered; change it if needed.
- If the list is correct, save it with Config OK.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Versatronik 200 installation and operating manual, p. 142. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.