Viessmann Boiler: Gas pressure switch 2 fault shutdown (leak test of safety valves)
Gas pressure switch 2 fault shutdown (leak test of safety valves) on a Viessmann boiler: Gas pressure switch 2 (red, VPS pressure) checks the gas safety valves for leakage each time the burner starts. Excessive leakage causes a fault shutdown.
Applies to: 750/1000 MBH burner (gas pressure switch 2)
Common causes of gas pressure switch 2 fault shutdown (leak test of safety valves)
- Leakage through the gas safety valves
- Faulty gas pressure switch 2
How to fix gas pressure switch 2 fault shutdown (leak test of safety valves): step by step
- Reset the burner control unit from the control unit and restart the burner.
- If fault 885 or 887 repeats, replace the gas solenoid valve.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 92. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.