Gas connection and gas train on a Viessmann boiler: A field-supplied service gas pressure regulator is required for all installations. Additional components may be required per local code (248-CMR-7:00, N.B.C., NFPA 54 and/or ANSI Z223.1). Gas shut-off valve size is 1 1/2 in. for models 399 to 1000 and 2 in. for models 1500 and 2000 (as printed, see notes). The gas train includes a built-in low gas pressure switch, electronic gas control valve, high gas pressure switch, test firing valve, direct spark ignition burner with venturi, and on 750/1000 a VPS pressure switch.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CI2 399 to 2000

How to fix gas connection and gas train: step by step

  1. Install a field-supplied gas shut-off valve upstream of the boiler.
  2. Install a field-supplied union on each side of the gas train as shown.
  3. Install a field-supplied service gas pressure regulator (required on all installations).
  4. Check gas shut-off valve size: 1 1/2 in. for models 399 to 1000; 2 in. for models 1500 and 2000.
  5. Verify the built-in low and high gas pressure switches and the test firing valve are in place before firing.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 installation instructions, p. 15, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.