Viessmann Boiler: Flue gas damper coding during commissioning
Flue gas damper coding during commissioning on a Viessmann boiler: Flue gas damper coding address 0a defaults to 0a:1 (damper fitted) in all applications. If no flue gas damper is used, set it to 0a:0. If it is not changed at the control unit during commissioning, the burner checks for a damper itself and the damper function can then only be set at the burner control.
Applies to: All Vitotronic 300 GW6B applications
How to fix flue gas damper coding during commissioning: step by step
- Check whether a flue gas damper is fitted.
- If none is fitted, set coding address 0a to 0a:0 during commissioning or on Coding level 1.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitotronic 300, GW6B installation and service instructions, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.