Viessmann Boiler: Flame goes out during operation (no fault display)
Flame goes out during operation (no fault display) on a Viessmann boiler: The flame extinguishes while running and no fault code is shown.
Applies to: Vitocrossal 200 CM2
Common causes of flame goes out during operation (no fault display)
- Inlet strainer of the gas valve contaminated
How to fix flame goes out during operation (no fault display): step by step
- Remove the flange.
- Clean the strainer.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.