Viessmann Boiler: Fixed high limit test (RTD sensors)
Fixed high limit test (RTD sensors) on a Viessmann boiler: Test the fixed 210°F (99°C) high limit by forcing a call for heat and throttling water flow. The burner should lock out at the limit. Viessmann is not responsible for overheating damage during this test.
Applies to: Vitocrossal 200 CM2 with GW6B control and GC310 burner control
How to fix fixed high limit test (rtd sensors): step by step
- Jumper terminals 2-3 of plug 146 on the GW6B control to simulate a call for heat. On GW6B cascade systems, use the emissions test switch instead (top left, ladder sign).
- Set coding address 9B (external heat demand) to a maximum of 241°F (116°C), higher than the fixed high limit. Skip this if using the emissions test switch.
- Set item #4 'Max. boiler water temperature' under menu 6 of the burner control (GC310) to 243°F (117°C), higher than the fixed high limit. Factory default is 203°F (95°C).
- Start the burner with the call for heat.
- Slowly throttle the water flow to the boiler.
- Watch the temperature on the GW6B control.
- When the fixed high limit is reached, the burner locks out with F F2 displayed. The fan runs for 10 minutes.
- Reset the fault manually only after boiler water temperature drops.
- Restore item #4 under submenu 6 and coding address 9B to original settings.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.