Viessmann Boiler: Fire response
Fire response on a Viessmann boiler: If the appliance is on fire, call the fire department. Only attempt to extinguish if qualified.
Applies to: Boiler room fire
How to fix fire response: step by step
- Call the fire department immediately.
- Shut down the boiler.
- Close fuel shutoff valves.
- Use a tested class ABC fire extinguisher only if qualified.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A service instructions, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.