Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Fill the heating system

Updated · by Aurora Star Tech Inc.

Fill the heating system on a Viessmann boiler: Fill the system through the boiler fill connection with the filling function.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

How to fix fill the heating system: step by step

  1. Flush the whole heating system before filling. Use potable water only.
  2. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
  3. Open system isolation valves at C and D if installed.
  4. Check the expansion tank pre-charge. If it is below system static pressure, raise it to just above system pressure.
  5. Connect a hose to the boiler fill tap and fill at boiler fill BF while draining air from boiler drain BD.
  6. Activate the filling function from the service menu and end it with OK.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

More commissioning tips for boiler

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair