Viessmann Boiler: Fill the heating system
Fill the heating system on a Viessmann boiler: Fill the system through the boiler fill connection with the filling function.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix fill the heating system: step by step
- Flush the whole heating system before filling. Use potable water only.
- Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
- Open system isolation valves at C and D if installed.
- Check the expansion tank pre-charge. If it is below system static pressure, raise it to just above system pressure.
- Connect a hose to the boiler fill tap and fill at boiler fill BF while draining air from boiler drain BD.
- Activate the filling function from the service menu and end it with OK.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.