Viessmann Boiler: Field contact requirements for digital inputs
Field contact requirements for digital inputs on a Viessmann boiler: External contacts must be floating (dry). Observe safety category II: 8.0 mm air and creep path, or 2.0 mm insulation thickness to live parts.
Applies to: Extension EA1 digital inputs
How to fix field contact requirements for digital inputs: step by step
- Use floating contacts only on DE1 to DE3.
- Keep the required clearances to live parts when wiring.
- For brief DHW recirculation pump operation, use a pushbutton contact on DE1, DE2 or DE3 and set the runtime with coding address 3D.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA service instructions, p. 91. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.