Viessmann Boiler: Enter the emissions/relay test mode

Updated · by Aurora Star Tech Inc.

Enter the emissions/relay test mode on a Viessmann boiler: Starts the CO2 test mode and shows the relay test status.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner control unit

How to fix enter the emissions/relay test mode: step by step

  1. Open the gas shut-off valve.
  2. Start the burner with the emissions test switch enabled at the boiler control unit.
  3. While the burner runs, press the two buttons shown on page 66 together and hold for more than 2 seconds.
  4. Status shows "P" (relay test). Service shows the modulation level in %: 100 = upper heating input, 0 = lower heating input.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More service & test modes tips for boiler

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 66. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.