Viessmann Boiler: Enter service menu and run actuator test
Enter service menu and run actuator test on a Viessmann boiler: Used to force the burner to low fire or high fire for combustion testing. The key pressed with OK is not legible in the source text.
Applies to: Service menu, actuator test
How to fix enter service menu and run actuator test: step by step
- Press OK and the second key together for about 4 seconds to open the service menu.
- Select Actuator test.
- Select Base load OFF to run low fire, or Full load OFF to run high fire.
- Select all actuators off to end the test.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.