Viessmann Boiler: Emissions test mode
Emissions test mode on a Viessmann boiler: Holds the boiler at a steady temperature for a short flue gas test.
Applies to: Boiler control board
How to fix emissions test mode: step by step
- Activate the emissions test switch on the Optolink/emissions test board.
- Burner switches on, and all pumps run.
- Mixing valve stays in its control mode.
- Boiler water is controlled by the adjustable high limit, which is set to 167 °F / 75 °C by default.
- Take flue gas readings during the short test window.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
More service & test modes tips for boiler
Source: Vitotronic 200 service instructions, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.