Viessmann Boiler: Emissions test mode for flue gas testing
Emissions test mode for flue gas testing on a Viessmann boiler: Briefly raises boiler water temperature for flue gas testing. Only the service technician should activate it, during the annual inspection.
Applies to: Vitotronic 300-K MW2C multi-boiler cascade
How to fix emissions test mode for flue gas testing: step by step
- Set the emissions test switch on the Vitotronic 300-K to the test position.
- The pumps start and the mixers stay in control function.
- Enable emissions test at the control unit of each boiler. The burner comes on and the boiler circuit pump starts.
- To end: set the emissions test switch back, or close the cover flap.
- Disable emissions test at the control unit of each boiler.
- Follow the applicable boiler operating instructions.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
MW1SVitotronic 300-K, type MW2B
More service & test modes tips for boiler
Source: Vitotronic 300-K MW2C operating instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.