Viessmann Boiler: Emissions test mode (flue gas measurement)
Emissions test mode (flue gas measurement) on a Viessmann boiler: The emissions test switch on the optolink/emissions board runs the boiler at a constant water temperature for a short time for flue gas measurement. The burner starts, all pumps run, the mixing valve stays in control mode, and boiler water temperature is held by the adjustable high limit.
Applies to: Vitotronic 200 KW2 boiler
How to fix emissions test mode (flue gas measurement): step by step
- Set the emissions test switch to its test position.
- Confirm the burner is firing and all pumps are running.
- Measure flue gas at the test point.
- Return the switch to normal operation when finished.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
More service & test modes tips for boiler
Source: Vitotronic 200 Service Instructions, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.