Viessmann Boiler: Direct vent sidewall termination height
Direct vent sidewall termination height on a Viessmann boiler: Vent termination must be at least 12 in (305 mm) above the anticipated snow level and placed so snow cannot block it. The termination must be installed with proper clearances per local codes or CAN/CSA-B149.1 or NFPA 54. Exposed PP(s) pipe and elbows outside must be UV resistant.
Applies to: Direct vent sidewall termination
Common causes of direct vent sidewall termination height
- Snow blocking the termination
How to fix direct vent sidewall termination height: step by step
- Set the sidewall termination at least 12 in (305 mm) above the anticipated snow level.
- Confirm the termination cannot be blocked by snow.
- Use UV resistant polypropylene for exposed PP(s) pipe and elbows.
- Install a stainless steel or plastic mesh screen on the intake terminal.
- Follow the vent maker's instructions for the sidewall kit.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Installation Instructions, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.